how i meggar value of 11kv alternator winding.and with meggar.
Answer Posted / kj
See extract from service manual for HV alternator.
A 5000V motorised megger or similar instrument should be
used. Separate the three neutral leads,
ground V and W leads and megger U to ground. Repeat for V
phase with U and W grounded and W
phase with U and V grounded. Minimum acceptable limits
after 1 minute for each phase are:
New machine 300 M
In-service machine 150 M
The insulation resistance should not be less than specified
and the polarisation index should be in the
order of 2 or greater at 20 ÂșC.
(PI = IR10min / IR1min)
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
PLZ sent the previous year question paper for GET in NHPC on my EMail id ppshanker@gmail.com
how to find the multiplication factor for digital energy meter and analog energy meter
what is cathodic protaction?
What information we need to prepare relay coordination chart
How to calculate no of EARTH PIT? Describe the formula as per IS standard?
how brushed dc motor operating ?
In what cases (circumstances)we should apply P controller, PD controller, PI controller & PID controller ?
What is the difference between acs 550 & acs 850
how is positive, negative, zero sequence is happen.. how is effect on 3 phase system
WHY THE COLOR OF OUTDOOR TRANSFORMER IS BLUE ONLY???
if the load is 80 amp for main fuse and 100 amp for breaker so how can we calculate the cable size (cooper ) .
what is the difference between elcb and rccb ?
I am having a 42KW 3 phase electrical heating furnace, heating element is 80/20 nichrome material, my connections is made in such a way that 2 star connection compromising 2 coils per phase so totally 12 coils, shall if i use it unbalanced star condition (instead of 2 group of 3 phase or 1 group of 3 phase, connecting 4 phases of 5 phases) what will be the consequences and is it acceptable?
explain why core loss of a transformer is almost constant under different load conditions when connected across a constant voltage and constant frequency.
Why have to use copper cable for local isolator to motor ?