is it possible to flow a current between nutral and earth
in a circuit? although nutral and earth having same
potential diffrence?
i=0/r=0A
if any body now any solid reason because i am getting a
triping problem in rcbo due to nutral and earth shorting???
Answer Posted / kj
The reason you are getting tripping of the RCBO is the way
the RCBO works.
The RCBO senses the current in the phase and neutral. As
long as these are balanced it will not trip. It is designed
to trip if there is an inbalance. This is usually a current
flow between the phase and earth which is then not returned
by way of the neutral.
When the is a short between the earth and the neutral it
provides a parallel circuit. Some of the current will flow
through the earth and some through the neutral as they are
now connected together on both sides of the RCBO. The RCBO
senses an inbalance because not all of the phase current is
flowing back thriough the neutral and it therefore trips.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
11000volt DG set carnt kaise banvay
detailed procedure how we calculate cost for pcc m10 and rcc m20 including centering and labour excluding steel/ iron
How much earthing frequency is capable?
which cable is used for 15 Hp monoblock pump 3phase and service wire Distance is 210 feet please tell me cable size Armaured
Can we put 3 layers of cable tray while installing tray
explain safety measures in alternator?
i am going to correct power factor of 1600kw induction motor,when i calculate capacitance of capacitor it is three time more in star connection than delta. if motor is star connected which connection i shall adopt for capacitors and reason for adopt this connection
how much value of resistance should connect to 15 kw, 6 pole 3 phase slip ring induction motor having RV-240, RA-42.
any one guide me to reduce the power factor of diesel Generator from 0.97 Leg to 0.8 Leg.with out any change in my load.
What is meant by time harmonics and space harmonics?
in india per day how much power is generated including all power station
HOW CAN YOU CALCULATE PRACTICAL EFFICIENCY OF A ASYNCHRONOUS INDUCTIONMOTOR OF 7.5KW,& MOTOR IS RUNNING WITH AVOLTAGE OF 410 VOLTS,& TAKING CURENT OF 13 AMPS
what is mean by D.O. in distribution line poles?
how to calculate fuse rating for a motor
I COMPLITED MY B.TECH AND 10TH CLASS WITH 70%MARKS BUT 12TH CLASS 55%MARKS..CAN I GET INDIAN RAILWAY RECUREMENT EXAMINATION?