How to isolate a DPT from line in the condition that process
must not be disturbed,and process is also critical and no
bypass is available.?
Answer Posted / muhammad arsalan afzal
isolate the transmitter from the main isolation valve and
follow this procedure.
First of all
1= Close high pressure manifold valve
2= open the equilizing valve
3= than close the low pressure manifold valve.
Mostly we we open equilizer valve when we are isolating
the tx. but what will happen if we close high side pressure
valve before equilizing valve? applied process Pressure is
already there on both sides of the transmitters no extra
pressure will be exerted on the tx because we are only
closing the valve. DP cell demage only in that case if we
purge high or low side before closing the manifold
isolation valves and we start closing the valve without
opening the equilizer.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....
What is rang ability?
why orfice is not used for main steam flow calculation
hi! i want to know about mpse exam.
pls suggest suitable MOC of diaphragm for pressure measurement of UREA grade solution service fluid.
Describe the functions of the Operator Interface including the considerations related to alarming and display layout/configuration/layers.
what would be the minimum flow rate that we can measure on rotameter..?
What is the working principle of the magnetic meter?
applications of plc in printing and packaging?
Why use ball valves on Gas pipelines instead of gate & or globe valves...means basic diffrence or use of these valves..how designers knows this type of valve with rating is required...
CONTROL VALVE OPERATING IN MANUAL BUT NOT IN MANUAL. WHAT SHOULD BE THE PROBLEM ?
what is the process for double acting cylinder pneumatic for 32' v/v
how to calculate signal cable sizing? and multipair cable sizing??explain in brief?
Good evening all I need a small favour regarding reliance paper i wanna probable sample papers(e&i) of reliance. if any of u have any idea about dis then plz mail me back.i belongs to electronics and instrumentation engg.so i need e&i papers. thanking u....
What is difference between ESD and PLC please Explain me clearly.