Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is PMG and AREP excitation system in generator

Answer Posted / suryaa

Electrical Power
Output
Sense
Main Stator Exciter
Stator
Exciter
Rotor
Mechanical
Rotational
Power Input
Diode
Bridge
Main Rotor
Set Reference
Output
AVR
Power
Auxilliary Coils
(Series and Shunt)
to give constant
power source
AVR14 – AREP
EXCITATION SYSTEM
The AREP excitation system improves the
voltage response of the generator during
transient load application, such as motor
starting. AREP also provides a sustained shortcircuit current for the operation of protective
devices. This option requires the standard selfexcited generator be replaced by a generator
that has been fitted with auxiliary AREP coils.
These coils provide excitation power to the AVR,
giving both shunt and compound (booster)
characteristics. Isolation of the excitation power
ensures that regulation is not affected by nonlinear distorting loads.
The Permanent Magnet Generator (PMG) is normally used
as a secondary exciter to supply constant voltage for an
Automatic Voltage Regulator (AVR). Because the PMG is
separately mounted on the generator shaft, the terminal
voltage will not affect the input voltage of the AVR, and it
can get stable energy without regard to the synchronous
generator.
• Improved transient performance
When the terminal voltage of a generator is reduced by appliying a significant load, the AVR input voltage is reduced
as well if a SHUNT excitation system is used. Therefore
sometimes the input energy is not enough for the AVR
to increase field current. However the PMG will provide
constant voltage for the AVR so that the field current can be
increased quickly to ensure the voltage dip is minimal and
remain within an acceptable range.
• Provide >300% sustaining short-circuit current
Under short-circuit conditions, it is necessary to sustain a minimum value of current in a sufficient time to ensure operation of
the system’s protective devices. Sustained short-circuit current
is achieved by the PMG excitation system.
• Increased non-linear loading ability
The non-linear load may produce harmonics for the generator
terminal voltage. These harmonics will affect AVR firing if the
AVR is supplied by terminal voltage. PMG is a separate generator, electrically isolated from terminal voltage, thus it can improve
AVR operation condition.
• Ensure remanence voltage to black starting
The permanent magnet mounted inside the PMG rotor can keep
a strong magnetic field for a long time. In generator black starting conditions, voltage can be built up by the PMG without

Is This Answer Correct ?    34 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why we change the direction of winding in rotor ?how we make the north and south pole?

2063


What is the dependency of stiffness on load angle??

1323


What are the functions of different probes used in cro?

1202


tan delta equation test on alternators

2228


How to Calculate Transformer Earthing Electrode Rod Size both Body and neutral Earthing ? Any Standard Formula? Please Suggted

1629


How you calculate the repturing capacity of a HRC fuse

2627


What is the role of Dedicated earthing in UPS System?

3107


What is kvar?

1340


Mention how NPN and PNP transistor works?

1290


at which voltage level arcing ground is occurs ??????????

2076


What is the difference between UPS & inverter ? which UPS is better and whos got the edge ? what is the difference between & inverter ? which UPS is better and whos got the edge 12 V , 24 V , 36 V etc what are the advantages of 12 V, 24 V , 36 V etc and what are the disadvantages of 12 V, 24 V, 36 V etc thanks

1910


please send the last 5 years {{{JUNIOR ENGINEER - ELECTICAL, ELECTRONICS RRB CHENNAI and secundrabad}}} TECHNICAL question papers TO MY EMAIL ID dinesh100701@gmail.com

2201


can anybody send the rrb chennai &rrb bopal question papers of 2006&2007.My exam is on 12 oct 2008.Its urgent

2051


how braking & making capacity of circuit breaker are calculated?

2308


what is the main parts of transformer? how it is functioning? pls giv the ans briefly.

1969