What are the point of a single core cable to be earthed?
Answer Posted / 7anoter4
The grounded point of a cable shield[or screen] could be :
1)at the supply side-usually is not necessary since the
supply side is enclosed
2)at the far end-is better for receiver security.
3)if the built-up voltage-due to induction produced from
the current flowing in the main conductor-is elevated [more
than 25 V usually limited]then a middle point grounded will
reduce this voltage to a half.
4)Both ends-if the middle point it will not reduce enough
the built-up voltage.
However, the circulating current will produce a
supplementary heating of the main conductor and then a
derating factor should be introduced.
There are also other means to overcome this by cross-
bonding the shield and even the main conductor, also.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What kinds of decision are made about CT from it's Knee point(voltage & current)?
how to compare with Relay settings for HT< panels, RMU panel, and PSS CSS transformer?? 1) Load amps, 2)Tripping time, 3) CT ratio, 4)Cable size 5) Transformer KVA rating 6) transformer full load amps
What are the parameters of water ( Water quality )to be monitored in Centralised HVAC ( water cooler chillers )
If a rotary UPS is in line through grid power; What would be the impact on Power Factor if the load through rotary ups is 25% , 50% , 75% & 100%. Will the power factor reduce with less load?
I am going to appear for the RRB Chennai Section Engineer online exam. Please send me the question papers from 2001 to date to my mail id:upendrakrishna20@gmail.com,plz send me ,or send any other rrb papers plzzzzzzzzzzzzzzzzzz
why the earth is taken minimum in supplying? wather it the proportional factor to getting work any equipment or a power plant?
what are the standard IR values should be of R-E, Y-E, B-E, R-Y, Y-B, B-R of VCB in closed condition and in open condition for 500KVA & 1000KVA transformers. and what is the acceptable range when tested by 5000V megger.
Is there any problem about which the drive (inverter) doesn't show/display the alarm and/or fault but instead of this , it doesn't work ? I want to know that could there be any kind of problem in the drive when the drive doesn't display the alarm and/or fault ?
How the circuit breaker is selected for Induction motor of 100 kW, 415 volt, 0.85 power factor, 0.95 efficiency ?
thyristor controlled APFC panel design parameter?
why electron produce magnetic field when it is in motion?
Why derivative controller is not used in control systems?
what are safety measures in /control in diesal engine/ explain them?
what do u understand about FACTS? how they are useful?
Yazaki india pvt ltd interview questions qurey related