1) Can anyone give me a typical value for Insulation
Resistance of 11kV xlpe cable?
2) How much will the IR value decrease per KM of cable
length added?
Answer Posted / 7anoter4
According to UL-1072 ch.57.5 insulation resistance of an
insulated conductor will be:
R=1000*K*log10(D/d)/L
D=insulated core diameter d=conductor diameter. L=cable
length.
The minimum permissible insulation resistance will be:
K=20000 Mohm/1000 ft. then L=cable length in ft. or K=6100
Mohm/km then L will be in m.
Let's say we have a 1*240 sqr.mm copper conductor 11 kV
XLPE insulated cable.
According to IEC 60502-2 [BS6622] insulation thickness=3.4
mm.
The conductor diameter is about 20 mm.
Then D=20+3.4*2=[approx.]27 mm.
R=1000*6100*log10(27/20)/m=7.95*10^5 Mohm/m or 795 Mohm/km.
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
How can we calculate the motor frame sizes?
how to determine the inrush current of a transformer
which cable is used for 15 Hp monoblock pump 3phase and service wire Distance is 210 feet please tell me cable size Armaured
a)In a 3-phase 4-wire circuit, a circuit breaker is selected to protect the circuit whose highest fault level is 6.6 MVA. Determine the required minimum breaking capacity in kA. (Note: Covert 3-phase power in terms of kA to find answer.) b)Using the below, determine the required minimum making capacity in kA as a “peak value”. Rate breaking capacity (Icn) ka: Icn<= 1.5 Factor = 1.41 1.5
Explain Need of a starter in a dc motor.? Also explain any two starting and speed control method of dc motor?
how can we select the type of wire.what factors we have to look on it , do we have some formula to calculate it. please guide me on it
How DC earth leakage currents can be reduced ?
can u give me a brief idea about power line carrier communication ??
How to calculate Air conditioning capacity for a telecom BTS shelter?
what do w do when the output of generator is fluctuating?
how we calculate the withstansing current capacity of wires&cables?
what is the meaning of vcc
at meter room 50 hrc switch installed,but there are not get earthing proper,so what happen?and 11kv transformer out put going in to hrc main 400a three nog each? so earthing is require for all switch? (some customer made earthing at there home.)
What are the major reasons for balancing hydro-thermal mix?
what happen when increase or decrease size of lamp,light.glass.