1) Can anyone give me a typical value for Insulation
Resistance of 11kV xlpe cable?
2) How much will the IR value decrease per KM of cable
length added?
Answer Posted / 7anoter4
According to UL-1072 ch.57.5 insulation resistance of an
insulated conductor will be:
R=1000*K*log10(D/d)/L
D=insulated core diameter d=conductor diameter. L=cable
length.
The minimum permissible insulation resistance will be:
K=20000 Mohm/1000 ft. then L=cable length in ft. or K=6100
Mohm/km then L will be in m.
Let's say we have a 1*240 sqr.mm copper conductor 11 kV
XLPE insulated cable.
According to IEC 60502-2 [BS6622] insulation thickness=3.4
mm.
The conductor diameter is about 20 mm.
Then D=20+3.4*2=[approx.]27 mm.
R=1000*6100*log10(27/20)/m=7.95*10^5 Mohm/m or 795 Mohm/km.
Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
Cb closed condition if there is a tcs fail whether cb will trip or not
Explain Need of a starter in a dc motor.? Also explain any two starting and speed control method of dc motor?
I'm looking for a softcopy manual set for a Credence ASL- 3000. Anyone know where I can get it?
hii this is ranjith from hyd... i want to know what type of questions they ask in interview...and hw the interview will go..? what subjects thay ask specially for electrical engg students?
Why front mounted CT polarities are always towards breaker?
What is the difference between the relay and the circuit breaker?
what do you mean by class PS CT and what are technical details needed for calculating it?
generally in LT and MV motors we are using 3.5Coresx16,25,35,50 etc cable for supply.although motors is earthed at two point and having all protection.then why we are using that 1/2 core for earthing the motors.while in HT cable we are using only 3core cable for motor supply.generally lt and mv motors are delta connected and ht motors having star connection.whethere it is having any relation with winding connection( star or delta).all motors i am talking about are dol only.can anybody solve my confusion.thanks...
What is resistance reading of earth copper rod with grid and without grid?
What is FM200 Gas??Applications........
An ELHNC 80amp 240v 30mA RCD is tripping periodically, every 30 - 180 seconds is it safe to disconnect the protection circuit?
WHAT SHOULD BE THE BEST CURRENT RATINGS (PRIMARY / SECONDARY)FOR A CT INSTALLED AT THE INCOMING 11KV PANE? WILL IT BE CALCULATED ON THE BASES OF MAXIMUM DEMANT VALUE OR ON SUM OF ALL TRANSFORMER'S KVA? NOMALLY MAX DEMAND REPRESENT THE MAXIMUM OPERATING LOAD OF THE PLANT AND TOTAL KVA OF (SAY 5 NUMBERS TRANSFORMERS) REPRESENT THE CONNECTED LOAD. WHICH i.e. MAX DEMAND KVA OR CONNECTED KVA ARE BETTER TO USE FOR CT CURRENT CALCULATION? PLEASE ANSWER.
How to apply 'c' license and also explain what is difference between 'c' and 'b'license.i am also working in one of the private company.i have finished my diploma in 2014 .i have already finished in ITI electrician course.....
If symmetrical fault occurs at the terminal of a synchronous motor then how the motor will act...explain it..
What are the conditions to be satisfied for parallel operation of dc generators?