why there is a fault occurs, if a phase wire touches ground..
and the fault not occurs when we connect a bulb between phase
and ground..??
Answer Posted / 7anoter4
Let's say the cable supplying the outlet [phase-neutral-
ground] is 3*14 awg copper and the length up to supply
panel is 300 ft. The conductor resistance is about 1 ohm[at
rated temperature].For 120 V voltage supply at panel if the
phase contact the grounding conductor the current will be
120/2=60 A. A 15A fuse will burn in less than 1 sec.
However, usually the short circuit current is 500-1000A.
If a bulb is connected between phase and ground ,for a 100
w bulb 120 V the resistance will be 120*120/100=144 ohm.
The current will be 120/144=0.83 A.
Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
would the same effect be achieved by reversing the connection to one winding of the induction motor 3-phase?
if the load is 80 amp for main fuse and 100 amp for breaker so how can we calculate the cable size (cooper ) .
How many energy meters can be connected on a 15VA Voltage transformer. please send a calculation sheet.
what is the eight bit unit?
what is the correct method for the outdoor termination of 19/33 KV HT cable step by step?
what is servo motor & how does it work.
what is formula to cal cute earth pit numbers and size of earth strip used in earthing?
What is float cum boost charging system?
how many types control panel of a 132/33 kv substation
Why reactors use before incoming of ac vvfd drive?
what is the use of power transformer in GSS.
Which type of motor is used in trains, what is the rating of supply used explain working principal?
How does a tertiary winding filter harmonic(espcially 3rd one) from entering into load system?
Whata are the types of Cables?
How to protect a Dosing pumps/any sensitive equipment (single phase) from surge protection inside a food factory.