why there is a fault occurs, if a phase wire touches ground..
and the fault not occurs when we connect a bulb between phase
and ground..??

Answer Posted / 7anoter4

Let's say the cable supplying the outlet [phase-neutral-
ground] is 3*14 awg copper and the length up to supply
panel is 300 ft. The conductor resistance is about 1 ohm[at
rated temperature].For 120 V voltage supply at panel if the
phase contact the grounding conductor the current will be
120/2=60 A. A 15A fuse will burn in less than 1 sec.
However, usually the short circuit current is 500-1000A.
If a bulb is connected between phase and ground ,for a 100
w bulb 120 V the resistance will be 120*120/100=144 ohm.
The current will be 120/144=0.83 A.

Is This Answer Correct ?    7 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

would the same effect be achieved by reversing the connection to one winding of the induction motor 3-phase?

1344


if the load is 80 amp for main fuse and 100 amp for breaker so how can we calculate the cable size (cooper ) .

1681


How many energy meters can be connected on a 15VA Voltage transformer. please send a calculation sheet.

1518


what is the eight bit unit?

1981


what is the correct method for the outdoor termination of 19/33 KV HT cable step by step?

1655






what is servo motor & how does it work.

1518


what is formula to cal cute earth pit numbers and size of earth strip used in earthing?

1806


What is float cum boost charging system?

1596


how many types control panel of a 132/33 kv substation

2241


Why reactors use before incoming of ac vvfd drive?

1389


what is the use of power transformer in GSS.

1984


Which type of motor is used in trains, what is the rating of supply used explain working principal?

795


How does a tertiary winding filter harmonic(espcially 3rd one) from entering into load system?

1379


Whata are the types of Cables?

1612


How to protect a Dosing pumps/any sensitive equipment (single phase) from surge protection inside a food factory.

1292