Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate the earthing conductor & no. of earth pits
required

Answer Posted / sudhakar.g

The earth resistance of single rod or pipe electrode is calculated as per IS 3040:
R=100x&#961;/2×3.14xL (loge(4xL/d))
Where:
&#961; = Resistivity of soil (&#937; meter),
L = Length of electrode (cm),
D = Diameter of electrode (cm)

Example:
Calculate number of CI earthing pipe of 100mm diameter, 3 meter length. System has fault current 50KA for 1 sec and soil resistivity is 72.44 &#937;-Meters.
Current Density At The Surface of Earth Electrode (As per IS 3043):
• Max. allowable current density I = 7.57×1000/(&#8730;&#961;xt) A/m2
• Max. allowable current density = 7.57×1000/(&#8730;72.44X1) = 889.419 A/m2
• Surface area of one 100mm dia. 3 meter Pipe = 2 x 3.14 x r x L = 2 x 3.14 x 0.05 x3 = 0.942 m2
• Max. current dissipated by one Earthing Pipe = Current Density x Surface area of electrode
• Max. current dissipated by one earthing pipe = 889.419x 0.942 = 837.83 A say 838 Amps
• Number of earthing pipe required = Fault Current / Max.current dissipated by one earthing pipe.
• Number of earthing pipe required = 50000/838 = 59.66 Say 60 No’s.
• Total number of earthing pipe required = 60 No’s.
• Resistance of earthing pipe (isolated) R = 100x&#961;/2×3.14xLx(loge (4XL/d))
• Resistance of earthing pipe (isolated) R = 100×72.44 /2×3.14x300x(loge (4X300/10)) = 7.99 &#937;/Pipe
• Overall resistance of 60 no of earthing pipe = 7.99/60 = 0.133 &#937;.


If you have any doubt regarding this ...pls mail me sudhakar28485@gmail.com

Is This Answer Correct ?    4 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the Surge for 1.1 Phase Induction Motor(For Eg.1Hp) 2.3 Phase Induction Motor(For Eg.1Hp) 3.AirConditioner(For Eg 1Ton) 4.Refrigerator(For Eg 180Ltr or 160kW) 5.Induction Cooker 4. Ceiling Fan

2025


Can you used moeller lzm1 mccb in a dc system with 125vdc and 20ka short circuit current , beside is it have 24 or 48 volt shunt ? Beside how long current can through from An MCB shunt contacts? (like Z7-AS 24 V)?

2047


what is the difference b/w ground & virtual ground?

2294


why swinburnes test cannot be performed on series machines?explain

2319


An automatic water heater is an example of which type of control system?

1145


What happen when neutral point connected to core balance current transformer? (Neutral point of an alternator of a 180KVA DG. Neutral point connected to CBCT means enter to the CBCT)

2251


sometime battery charged and then automatically charged when rectifier ON conition, is there any chances please clarify the same.

1848


what is feeder bay?

1558


How to determine stage of Automatic Power factor controlling Relay(Apfcr)?

2140


how to deside the capacity of chock for drive?

2021


why motor range is available 22kv,30kv,37kv,45kv and so on? why motor range is not available 21kv,24,25,26,27kv and so on?

2771


How to calculate the fuse rating depend upon the DC circuit?

2829


What is method of calculating the fault current for a MDB, 50KW, 3PH, 415V, 50HZ?

2117


What kind of maintenance is conducted for Transformer

2243


how to calculate vfd o/p voltage by frequency

2139