This is about the recent problem that we have faced in our
project site.
We have 6/7.5 MVA. 66/11kV three phase star - star power
transformer. The neutral was solidly connected to the
earthing mat. But because of high resistance of earthing
mat (130 ohm on LV and 180 ohm on HV), one day LV side
neutral earthing conductor melted and we had a huge damage.
Can any one plz tell me what might happen when we connect
power transformer neutral to the earthing mat which has
high resistance (>100 ohm ) ?????
Answer Posted / k.prakashchandra
Have you measured IR properly, as the values are very high
?The IR should not exceed 2 ohms for a 66 KV MUSS .I do not
know whether primary neutral is to be earthed in case of
star/star tr.It is stated that LV side IR is 130 ohms ,and
hence the maximum earth fault current will be 50A.For 7.5
MVA tr the rated LV line current is about 400 A and EFR is
likely to be set at 80A.It appears that the earth wire
melted due to continuous earth fault current.If there is
conductor to ground fault at a distance of 100 m from tr
earthing ,there will be a pd of 63.5 V /m along the line
between the fault point and the neutral earth. If anybody
stands barefooted with feet 1 m apart along this line, he is
likely to be electrocuted as the power line does not
trip.Further the ground around the earthing also may be at
nearly phase voltage during earth fault
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What will happen if i used 11KV earth ht kit to 11 KV / 11 KV cable termination?
what mean by analog ,digital,numerical meters and relays? say the example?
what is the purpose of slope in the differential relay?why we are using two slope?but in busbar differential we are using only one slope.why?
Why space heater is required for each verical bus bar chamber? if one space heater is adequate or not for anti condensation?
Usually in the L & T make MCC feeders' power circuit,we have BMR after the MAIN CONTACTOR.,can we interchange their position, keeping the control logic same???
in star-delta tranformer,if the input of star connection is 400/7v 3 kva then what is the output of delta connection?
If I bring a basic electric meter from the States and hook it up in Costa Rica in a development that has only one transformer for the 50 homes, will it still be accurate regarding the usage of kilowatt hours?
why servomotor motor? where i apply for best output?
state basic meaning of 'INDUSTIAL AUTOMATION'?
What is the accepted limit to increase the choosen transformer capacity over the load and why ?
hii this is ranjith from hyd... i want to know what type of questions they ask in interview...and hw the interview will go..? what subjects thay ask specially for electrical engg students?
what is the calculation method to design core and winding of a 200kva 3phase distribution transformer?
What is referred to the electron in the outer orbit?
Why do we avoid electrical conduits in floors at apartments?
For the requirement of a furnace of temperature range up to 1200 oC using silicon carbide rods, What is the required rate of transformer needed (please do it with all details)?