what is STUB protection in tranmission system and switch
yard area?
Answer Posted / m. usman ali
During a line open condition with the station breakers
closed, the bus between the station breakers and line
disconnect for ring bus and breaker and a half/third
configurations may not be protected. The line protection
system shall be capable of protecting the open stub through
the use of overcurrent protection. This protection shall
also function correctly for the case where the potential
transformers for the line protection are located on the
line side of line disconnect whether or not the line is
energized from the remote end.
| Is This Answer Correct ? | 4 Yes | 6 No |
Post New Answer View All Answers
HOW DO I CALCULATE THE SETTINGS FOR THE DIFFERENTIAL PROTECTION OF A 12kV/6.6kV, 6MVA,DYN11 XMER WITH PRIMARY SIDE CTR 400/1 AND SEC SIDE CTR 600/1?
Compare salient pole and cylindrical rotor machines.
how to measure the current by compact digital equipment with dislay which fit inside any equipment
What is the difference between cylindrical-type and sandwich-type winding?
What is the form name of 'c' license, I want to download in web
What is milivolt dop test in Busducts? What is its significance & procedure to do the test?
In Designing the rating & accessories of a MCCB how to choose the type of releases..means what is the basis for selecting, thermal magnetic, electromagnetic & microprocessr based releases
difference between a diode and thyristor?
i have interview in Pepsi company what type of question will ask please send the question and answeer
while doing high voltage test on 11kv/433 distribution transformer why we only give 28 kv on hv side and 3kv on lv side for power transformers what is the value what factors it depends
block diagram of 2 ups system connected in hot stand by mode?
what is the saturation point of crgo lamination.
why we are using earth pit in sub stations.?
How do i carry out or know the vector group of a Dyn1 and Dyn5 transformer
which types of relay used in acb and vcb?