how much capacity(rating) of generator required to operate a
load of 100kv.

Answer Posted / abhishek jha

rating depends on wattage rating and not on volts. also if
it is 100 kw then if its power factor is assumed to be 0.8
then to supply that load ganerator rating should be
100/.8=125

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why we permissive overreach in distance protection.where it is applicable to use in long r short lines

2301


What are the causes for the failures of sandwich type (Al) busducts?

1433


How is magnetic leakage reduced?

727


grr resistance & contrator malt continuous

1680


How it can worked plc based electrical system And which type of software using.

1677






How to calculate the phase to phase clearness of HT /// LT bus bar?????

1600


what is the efficiency of thyristor

1130


i applied for c licence with my one year apperents trainee and i have attaced with A grade contractor company experiance that is for 14 monts experiance this document is sufeicant for c licence? pls tell why they rejected

1708


What is the Good Earth resistance value of G.I & Cu. Chemical Earthing & Normal Pipe Earthing?

1879


How to maintain ac plant?

1530


i need to give section engineer (electrical engineer) for RRB. Please suggest some book

1458


how to put cable sizing and cable glands size for respective cable & Cable Lug size in a DB sectors???

1657


v/f drive basic princeple

2004


If more than rated DC voltage appears across trip coil of the breaker, what will happen? e.g. in 110V DC circuit system, if voltage across battery terminal showing 121 V

1199


what is the difference between b c d curves on mcb

1346