In control valve , Failure position : Close
If it is Fail close(FC) during failure of AIR.. what will be the initial/ normal position of control valve is it normally open or close? please some one explain soon..
Answer Posted / bhargav purohit
Hi,
I think your question has it self an answer. Your valve is Air fail to close. Means if there is no Control Air/signal, your valve will be closed .
In running plant condition, Position of valve could be anything according to process.( Fail to open or close depends on process requirement)
Suppose you want maintain a Tank level and safe condition is full tank, then..
1> if you are maintaining level by inlet water flow to tank, your valve should be Fail to open. Means in case of signal failure your valve will open and fill the tank (Safe condition)
2>If you are maintaining level by output flow, then you should select fail to close vale. So in case of failure of control signal, output flow will be closed and tank will be full.
Regards,
Bhargav Purohit
| Is This Answer Correct ? | 12 Yes | 0 No |
Post New Answer View All Answers
Which is the best field foundation bus. ( FF ) Yokogawa, Honeywell or others ?
What is the diffrence between digital signal processing and discrete signal processing?
1.what is the effect of vapour presuure in orifice plate flow measurement 2.which is more effective 2 pressure sensors or one single differential pressure sensor in orifice plate measurement 3.how to design a v/i converter and i/v converter 4.how many type of thermocouple are there 5.how many leads are there in thermocouple measurement 6.how pressure sensors are connected in level measurement in differential pressure method 7.what is the output of capacitive pressure sensor (ac or dc),how its o/p is signal charactarized 8.what is the physical meaning of discharge coeeficient,why it is calculated,orifice plate what is its value,why it is less than 1,Q at upstream is equal to or not equal to Q at downstream of orifice plate why?what is vena contracta in orifice plate 9.why rotameter is called variable area flowmeter,it can measure flow even if area is not varying,why it is made tapered 10.design a 10 bit counter ,which counter you will prefer 11.how to remove self heating error in RTD 12.which is more sensitive pt100 or pt50 13.why thermocouple are connected in parallel 14.what is lead contact error in RTD,how to avoid 15.what is P,PI,PID,PD controller,why there is no ID controller 16.what is override,split range,sequential,ratio,feedforward,cascade controller 17.why we moved from SR to JK and then JK to master slave JK flipflop,give correct reason 18.how to measure level of a closed container which contains vapour and liquid,remember no vapour gas should be leaked,so ultrasonic and capacitive is not an option,design another method 19.how to design horse race counter including sensors and signal conditioning element 20.what is bevelling
How to Calibrate Level Switch in field
Explain the working of an enraf level gauge.
If a warning lamp will operate with the ground circuit is bypassed with a jumper wire to ground, what should you check?
I will attend an interview with GasGas company for a position of Instrument Technician ( Offshore )in next month can anyone tell me what questions they will ask. Thanks in advance.
any body please send me the old question papers of ongc test.
what is controlling card in dcs? how u measure dcs memory?what is bus in dcs?how u know dcs speed n ehternet speed?
What is difference of fanuc alpha series 16i and 18i controller.also what is differnce betn TC and MC controller
how many types of preheaters are in cement industry & what r they can any body explain?
what deference between panel earth and systemearth
how can leve transmetter calibate in feild .and also put cv and flow plz .....
few questions on RS 232,1 question on relationship of impedance and turns ratio, many questions on flowmeters
For crude application in floating roof tank, how to calibrate a DP Transmitter? How is the floating roof weight considered?