how many frequent start/stop operation possible in case of
HT MOTORS.
Answer Posted / dushyant patel
Depend upon the thermal characteristic of the winding and
type of insulation and cooling system provided maximum start
from the cold is allowed 3 withing an hour.
Due to 7 to 10 times of starting current winding requires to
be cooled. Thermal capacity used is provided by the smart
motor protection relays and that relay is not allowed to
start the motor until and unless thermal capacity after
cooling down is reset.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
explain single phase series motor
WHY EARTHING NOT NEEDED IN BATTERY IN SUBSTATION
XYZ
What do you mean by a phase angel of instrument transformer?
1.how many earth pits are required for 1000 k.w plant include substion , transformer ? 2. how many earth pits are required for 500kva generator.what is formula to calcute?
how many safety really of DG sets.
should %impedance be high or low in a power transformer? if so why?
I WANT TO know WHICH WAY IS BETTER FOR CONNECTION BETWEEN POWER TRANSFORMER AND MAIN DISTRIBUTION PANEL. 1-IS BETTER WE USE CABLE? 2-IS BETTER WE USE BUS DUCT? my transformer rate power is 2500KVA
what is the Transformer Impedence?How can calculate?
What is step signal?
What is the formula to calculate the rating of a three phase miniature circuit breaker
What is stacking factor? What is its approximate value?
what is the effect of back reactive power on the generator ?
I have doubt that the supply HZ (very low or high than rated ) may affect the power factor. is it true. ?
A 1F capacitor is charged to 100V initially. A 1H inductor is connected accros the capacitor througha a switch. The current in the circiut when the switch is closed is____