what is ZERO SUPPRESION and ZERO ELEVATION?
Answer Posted / rizwan afzal
Suppression.If transmitter is installed in such
configuration that positive pressure is acting on the HP
side even when level in tank is zero. Such as Tx is
installed below datum point then head pressure of impulse
line is always acting on the HP side of the Tx even if tank
is empty, to componsate that head pressure a -ve biasing is
applied which is equal to the head pressure.
IN OTHER WORDS the LRV of Tx is kept at +ve pressure(equal
to head pressure causing error), so that Tx should give 4mA
at that head pressure.
Elevation.If transmitter is installed in such configuration
that positive pressure is acting on the LP side(DP is in -
ve value when level in tank is zero). Such as Tx is
installed in wet leg configuration then head pressure of
wet leg is always acting on the LP side of the Tx (even if
tank is empty), to componsate that head pressure a +ve
biasing is applied.
IN OTHER WORDS the LRV of Tx is kept at -ve pressure(equal
to head pressure causing error), so that Tx should give 4mA
at that head pressure.
Or to keep range in +ve, Tx can be installed in such manner
that LP side is connected with datum point and HP side with
Wet leg.
| Is This Answer Correct ? | 23 Yes | 0 No |
Post New Answer View All Answers
Why MUX JB's are using only Temperature Element in Fundation field bus?
Explain the difference between plc and cnc?
please tel me the calibration of pneumatic controler.
which type inter lock use in petrochemical refinery,and oil & gas?
3. Differentiate between ultrasonic flowmeter and radar type flow meter.
what is the PC interface and software for connection to ABB logic module “ LM011-CE18RAC “ ( for Programming ) ??
Exothermic reaction./ endothermic reaction
In power plant to measure vibration of a turbine we install sensors. Before install this sensor we have to set gap voltage. What is meant by gap voltage and its use?
I want to know about DDCMIS in detail ? please explain it. Also give name of reference books in which it is explained in detail in very simple manner.
What is ultrasonic flowmeter?
What is the difference between ff transmitter and non ff transmitter
I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?
Can combine control system for Emergency control system (ESD)and Fire & Gas System ( F & G) is possble to built and offer to client? Can such system is as per Norms in India?
Can anyone convert a 5/2 way or 3/2 way valve into an ISO valve?
Linear amplifier.