why we use to transmit the power in three phases intead of
single phase ?

Answer Posted / paul

I do not think the previous answer is correct. Three phase is more efficient (Power In v Power Out) in respect to AC motors, and is also more cost economical in regards to power transmission as less copper is required for the same delivered power (given the 3 phase line voltage is taken as being he same as the equivalent single phase voltage therefore allowing the use of cable with the same voltage rating), however..

The transmission power loss (and therefor transmission efficiency) in a three phase systems is the same as in a single phase system (again, assuming same total load power and line voltage).

The previous response has omitted the fact that, even though there is no neutral wire the return current in a three phase system will be subject to I^2*R losses in the associated conductors. Taking R as the loop resistance (supply and return), a single phase system power loss can be calculated as I^2*R. For a balanced three phase system, the single phase equivalent losses will be ((I/root3)^2)*R. Therefore total losses = 3*((I/root3)^2)*R = I^2*R.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why should the lowest unit of a testing transformer ( cascaded transformer ) have higher power rating??

1887


How to design a Unit auxiliary transformer for a power house having a unit of 65 MW and Generating voltage of 11 KV and Secondary voltage of 433V

1672


1 hp is equal to how much watt?

730


Why 11kv to be generated in generation station

1258


please give me all the Alarm .Trip ,Safety Relays & Conditions of Chiller mail me on ashokbabunhce@gmail.com

1366






What is UPS and How do you maintain the UPS Maintenance? Brief Description on UPS maintenance.

2145


how does WTI work ?

1538


Explain Energy and Power signals?

1289


we are having 15kw and 3kw motor both can run in same time , instead of using copper we are using ug aluminium cable , 35 sq.mm is suitable for its current carrying capacity..?

1331


can anyone tell me can the electromagnetic waves can be reflected back?if so how &by which material it can be reflected back?please tell me so that it can help to my wireless power trasnmission device.

1366


What's mean HVF & HAF in Vacuum Circuit Breaker?

4748


how hazordious area is classified at an oil & gas plant and categorise suitable class of electric equipment in that area like induction motors, LCS, Lighting Fixtures Fluerescent/Flood lights Mercury& sodium lights, J.Bs, Power Cables etc

1362


For some transformers we are using solid neutral earthing while some others we are using resistance earthing why ?

1480


How would your past experience translate into success in this job?

6465


what is diff. between earthing grid,earthing mess, earting grid?

1881