3 ph motor connected in star delta starter. when we start
the motor it run in star but when in is going in delta it
trips the main incoming supply. why?
Answer Posted / deepak r thakur
simple when motor start in star three phase going to
winding correctly but when its going in delta motor two
winding connect with 440votl but 3rd winding connect same
phase so motor going in singal phasing & its get heavy
currunt it trips the main incoming supply.
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
what will be d.g. capacity to cater together for 14hp A.C. load & 3kw lighting load
i am going to give the JSEB,RANCHI exam for power plant,so i need some samples of papers related to that,so please send me these papers by my mail id.
Cables Construction hi friends, 0.6/1/1.2 kV LV , DC and Control cables are concentric copper conductor what does its means and what is the use of concentric copper conductor,and are this with copper tape shield or copper screening, ? thanks
Capacitor is load free component but why ampere meter shows current when capacitor bank breaker close?
what is meant by directional earth fault and non directional earth fault? describe both.
Whether it is possible to measure energy at the input of rectifier transformer (12 pulse with very high odd harmonics)
what is the function of statics switch in ups and tell me parts
how to choose cable size with respect to load? how to convert cable size in mm2 to sq.mm?
could anybody able 2 send me jindal steels previous papers fr electrical steam....pls send 2 my id if possible....sirisha.shaik@gmail.com
how to changeover ups in this power failur time?
hr round
What is the minimum underground tank size capacity considered for firefighting purpose?
transformer spections :: input voltage 0-110-230v; output volage 0-10-12-14v; amp=3A using CRNO CORE, capcaity=50VA primary turns = ? ; secondry turns =?
Explain few advantages of electric traction system?
what is the main difference between power devices and signal devices