why the generating voltage in India is 11kV or why is it be
transmitted as multiples of 11
Answer Posted / ashish
In Electrical Generation plants, the generation voltage will
be in the range between 11kV and 33kV. Generator designers
wishes to generate the electricity at high voltages as
possible to limit the stator current required to achieve the
desired output. But certain technical and economical
problems will arise which results in designing the generator
for particular voltage and current ratings.
• Low voltage generation for particular power level (say
500MW) requires large size of the stator conductors as huge
currents flow through the stator because of low voltage. (
Any current carrying conductor size is decided by the amount
of current flowing through the conductors). Thereby increase
in the cost and size of the machine takes place.
• On the other hand, increase of the machine voltage
significantly beyond the minimum necessary value results in
more insulation required on the generator stator windings,
thus increasing its size and cost.
Therefore an optimum value of Voltage and Current values are
attained for designing the generator considering the cost
and size factors of the generator.
Example:
660 MW generation plant usually operate at 23.5 kV with line
currents of about 19 000 A at 0.85 power factor.
Is This Answer Correct ? | 37 Yes | 5 No |
Post New Answer View All Answers
what should be the ideal gauge of wire (In sq mm) for different loads in Ampere?
Can we transmit digital signal to long distance ?
what is effect of 5amp fuse on 2mva pry protection of transformer
Showing results for capital, machinery, stock,wages, carriage in words, salaries, factory rent, repairs, fuel and power, buildings, debtors, sales, purchases, creditors, return outwords, return inwords, drawings, discount allowed, discount receivable, office expenses, bills payable, bills receivable, cash in hand, cash at bank, office rent comes under debit or credit
What is stacking factor? What is its approximate value?
how we can do the insulation on secondary of ct explain and so that tan delta will within limit
i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.
What is the resonant peak?
how is positive, negative, zero sequence is happen.. how is effect on 3 phase system
How LT megger works ?
i want to run 11kv star connected motor in 6.6kv with delta connected throught inverter, is it possible?
why do we carry out winding resistance test?
In dc ckt. 24v or 110v, which one is more efficient and why?
write a program that prints prime numbers from 1-20 in digonal form
What is main cause of cable's terminal point burned in Lug on high temperature although lug and cable selection is ok as per stantard and also tightness is ok as per situation. so please take in deep and tell correct answer thanku.