Answer Posted / a s nath
Local Breaker Backup (LBB) or Breaker Failure Pretection is
associated with Busbar Protection. If breaker fails to
operate due to its inoperable condition in spite of
operation of protective relays, there will be damage to the
system.This condition is being monitored by LBB relay or
BFR relay (Breaker Failure Relay)and will initiate the
Busbar protection and thus clears the bus.
The LBB protection will operate under the following
conditions:
(i) Lockout relay should operate
(ii)Current shall be more than 20% of normal current rating
(iii) The above currents shall persist after a time,
generally 200ms
When all the three conditions satisfy,it is considered that
the breaker is stuck and LBB protection will operate to
clear the bus.
By A S Nath
| Is This Answer Correct ? | 117 Yes | 8 No |
Post New Answer View All Answers
WHY RATING OF VCB NOT LESS THAN 630A
Define transfer function?
what is the differation bewreen kwh & fundamental kwh in electronic trivector meters
sir i have a car stereo system and there is jack on him so can u tell me a way to find out their power terminals on the jack or on the circuit board"
where the lexical paramater will use in fron end?
what is feed back and what are feed back amplifiers?
What is a differential amplifier? Also, explain cmrr.
what's prime importance of protection in electrical system.if protection system don't work properly what can happen in electrical system?
Why can't we parallel Voltage transformer secondary circuits?
what will happen reduce the transformer voltage from 415v to 406v, is it save the energy,? are this methodis good to reduce the energy.?
In ups static switch if i gives the supply at output end it will open the circuit in stactic switch or not if it will open then how it operates.
WHAT IS LOAD CELL
Is there any standard guidelines/Criteria to design NGR/NGT.?
why in a swquence network representation, the negetive sequence generated voltage is taken as zero?
What Is Connection APFC Panel In Compony.