Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Is there any problem ,if R-Y-B voltage is constant , but
the air compressor taking one phase high current.what is
possible causes.the said compressor is very new.(55kw).

Answer Posted / daxity

Obviously there is problem because the currents are not
balanced.the cause might be an imbalance in the winding
resistance which might come from unequal number of turns or
deffective insulation on that particular phase,or loose
connections on that phase from point of supply to the last
termination.........if the windings are perfectly
balanced:-misalignement and bearing failure can affect all
the phases.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

The electrical energy required to raise the tempreture of a given amount water is 200 kwh. If the heat losses are 20%, the energy required is?

1954


i have completed deee and i've (June2012-feb 2015 experience in electrical maintenance in pvt ltd company.company having HT & LT electrical power.how to apply electrical C-license ,NOW I was resigned my job,what are requirements of applying for c-license

1671


What is the formulae of Megger value for a A.C.Motor

2815


What safety precaution are to be taken for avoiding electric hazards ?

1808


lenz law application and define

2769


Will any motor burn if voltage provided is lesser than the rated voltage???? If yes, then how is speed control possible with voltage control

2107


why Y CONNECTION IS BETTER INTERMS OF EFFICIENCY AND P.F FOR A LAOD LESS THAN 40% AND WHY AFTER DELTA IS BETTER FOR > 40%

1884


What should be setting for alarm,tripping and cooling fan on for power transformer's oil temp. and winding temp. indicator?

1902


current transformer balance the power level on both sides. e.g in case of step up, at secondary side voltage rise but current decrease and vice versa in case of step down transformer. but how this power level remains same in case of current transformer and voltage transformer

1548


What are the reasons for the parallel operation of transformers?

1077


Why is the air gap between the pole pieces and the armature kept very small?

1336


What kind of socket shall be provided for window type air conditioner with cooling capacity upto 18000 BTU/hr

1020


What is an order of a system.

1259


in general it is observed in power stations, the tertiary winding is used in higher rating Y-Y auto transformer but not in Y-Y power transformer. is the tertiary winding is compulsory then why it is not using in power transformer 

1749


Transformer how to maintaince a check b check c check d check

2041