Is there any problem ,if R-Y-B voltage is constant , but
the air compressor taking one phase high current.what is
possible causes.the said compressor is very new.(55kw).
Answer Posted / daxity
Obviously there is problem because the currents are not
balanced.the cause might be an imbalance in the winding
resistance which might come from unequal number of turns or
deffective insulation on that particular phase,or loose
connections on that phase from point of supply to the last
termination.........if the windings are perfectly
balanced:-misalignement and bearing failure can affect all
the phases.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
what are the values of VRY,VYB,VBR,Vry,Vyb,Vbr,Vrn,Vyn,Vbn for Magenetic balance test of 100 KVA and 63 KVA Distribution transformer
What is turn ratio of a transformer?
how to calculate the magnetizing current of ct ( 800A/1A) for Relay 64
Post possible questions for Power Factor Panel FAT / SAT
what is the minimum recommended leakage current of an earthed cable connected to the body or skid of an alternator
How to calculate earth fault current for 6.6 KV , 50 HZ , 756 Amps , 3000 RPM , 0.8 PF generator
What are the different circuits in thermal power plant?
What is the tube exial fan?
what transformer we used normally and upto which kva?
Differenciate between circuit wiring and sub main wiring with illustrations
why the neutral point in connnection oscillates?
how many current required for hypo test
what is meaning of sympathetic tripping with respect to relays and give the values for current carrying capacities for copper and aluminium cables from 16sq mm to 500sq mm
when the Transmission and Distribution network where is the "feeder" lines are located? and why should be used in T&D network.....
is there any current and voltage drop on liquid resistance starter water/soda tank ?