Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

( Re: WHAT SHOULD BE THE RATING OF MCCB FOR 415V,3Ph,50KVAR
CAPACITOR BANK
Answer
# 1 The capacitor current would be kvar x 1000 / (415 x
sqrt3). This would be 70a approx. The MCCB selected should
have *atleast 1.4 times this current i.e. 1.4 x 70= 98. So
you should choose at least 100 A mccb.)
regarding to this answer,i would like to know why the
current have to times 1.4 to get the right amphere for the
mccb.hows the formula to get the 1.4??tq

Answer Posted / kimberly0617

if the capacitor bank is 525v??izzit the calculation same
as 440v??

Is This Answer Correct ?    0 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

HOW TO TEST A LIGHTENING ARREST ER ?

2200


we have consol make 3 phase servo stabilizer for cnc m/c. while installing the earth neutral voltage is 1.7 volts at stbilizer off condition and when stabilizer get on en voltage reaches 4.8 volts (new earthing is done and neutral is helthy condition all phase to neutral volts 440,442,441 v)why this happen.solution for cause.

7120


hi, in the event earth grounding is not available in a project, is there any other way to make the elcb work? fyi, i have an instant water heater (6.5kw) installed, however if there is grounding in the heating element inside the heater assembly, i will get grounded. thank you in advance to those who will answer my question.

1993


Draw transformer phasor diagram.(full load,no load)

4180


what is the string efficiency

5251


What is process of anneling transformer core

1966


What is meant by reset level of the relay?

1212


difference between a diode and thyristor?

2241


how to find the multiplication factor for digital energy meter and analog energy meter

2208


1.how many earth pits are required for 1000 k.w plant include substion , transformer ? 2. how many earth pits are required for 500kva generator.what is formula to calcute?

2918


how can see the ac indoor or out door ac which Tr

2016


sir pls tell me . our ct specifications are 120/5 ,2 core , 0.2 and 5p10 class , 30va and 30va buden. insted of 30 va i want use 15 va. can i use?

1516


please explain how to do 'pole drop test' on generator?

2911


Which type of air compressor is used now a days in the market. Keeping in mind of energy efficiency and maintenance points. Relevant documents may also be sent on mentioned email ids.

1674


How to calculate earth fault current for 6.6 KV , 50 HZ , 756 Amps , 3000 RPM , 0.8 PF generator

2053