( Re: WHAT SHOULD BE THE RATING OF MCCB FOR 415V,3Ph,50KVAR
CAPACITOR BANK
Answer
# 1 The capacitor current would be kvar x 1000 / (415 x
sqrt3). This would be 70a approx. The MCCB selected should
have *atleast 1.4 times this current i.e. 1.4 x 70= 98. So
you should choose at least 100 A mccb.)
regarding to this answer,i would like to know why the
current have to times 1.4 to get the right amphere for the
mccb.hows the formula to get the 1.4??tq
Answer Posted / kimberly0617
if the capacitor bank is 525v??izzit the calculation same
as 440v??
| Is This Answer Correct ? | 0 Yes | 4 No |
Post New Answer View All Answers
How the annunciator works ? How to do its wiring
What is highest size of HT motor like 11 kv or 33 kv,and how to make it 750 rpm.i think the size will be very big.any idea ? pl. reply..
can i connect the two phases of scott connected transformer,if not why?
what is transient enclosure vltage , very fast transients, very fast transient over voltages
what is the purpose of using filters in a protective relaying scheme?
what is the Earth Voltages in Power Plants, Sub-stations, Industries, Residential & Commercial Buildings.
what is buffer resistance starter.?.What is the working principle and where it is used..?
there is an alternator 480 k.w, 400v,50hz, 4-wire running on load having leakage alternator body earthed current 38 A. is it within acceptable limit? if yes then give reference if no then how to bring within specified limit
What is the one main difference between ups & inverter ? And electrical engineering & electronics engineering ?
hi, could someone help me to find a control design for syncronising panel .
A 400KVA transformer has 400 Hz frequency. If the frequency is changed to 50 Hz, then what will be the new KVA rating?
How to confirm the Phase shifting Transformer VECTOR GROUP relation , as below ZNy11.45d10.45-ZNYy0.15d11.15
Distinguish between nuclear power station with thermal power station for initial cost, starting period, cleanliness, and transportation of fuel
what is the criteria for selecting fuse rating in 1phase, 2phase & 3phase welding sets?
how can i find cable size from current rating?