Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

( Re: WHAT SHOULD BE THE RATING OF MCCB FOR 415V,3Ph,50KVAR
CAPACITOR BANK
Answer
# 1 The capacitor current would be kvar x 1000 / (415 x
sqrt3). This would be 70a approx. The MCCB selected should
have *atleast 1.4 times this current i.e. 1.4 x 70= 98. So
you should choose at least 100 A mccb.)
regarding to this answer,i would like to know why the
current have to times 1.4 to get the right amphere for the
mccb.hows the formula to get the 1.4??tq

Answer Posted / kimberly0617

if the capacitor bank is 525v??izzit the calculation same
as 440v??

Is This Answer Correct ?    0 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Name the component u would expect to find in a switchgear assembly?

2024


In a synchronous motor. if start is running at high speed.  What will be the starting torque : Higher Lower Zero

1715


how to set relay setting? and example calculation...

2030


When lag/lead/lag-lead compensation is employed?

1186


Igfet is a

1632


How to arrange a hous hold earthing system to keep minimum earth resistance( below 7ohms).

2172


what is buffer resistance starter.?.What is the working principle and where it is used..?

2027


Is RTCC panel needs any control supply.

2038


ratings of lightning arrester

2041


Why the arms of delta in a delta-wye power transmission system are kept constant??

1866


How to select, design,size & calculate for 11 KV/33KV/66KV/132KV/220 KV/440 KV circuit breaker for HT side of transformer protection/HT distribution protection?

2751


in what type of applications v can use q meter?

2123


PLZ EXPLIN ABOUT CLASS PS CLASS CT .WHY THEY R DESINED AND FOR WHAT PURPOSE?WHY OTHER CT CANT BE USED AS PS CLASS CT? EXPLAIN IN SIMPLE LAUNGAGE IF POSSIBLE PLZ GIVE CIRCIT DIAGRAM?EMAIL-RAJ_SINGH_0376@SIFY.COM

2260


is the value of inductance depends upon the value of thitha in doubly excited machine??

2022


What are locations arc protection relay is fixed.

1862