WHAT IS RMU AND WHAT IS ITS FUNCTION AND HOW TODISCONNECT
Answer Posted / apu basak
Ring Main Units
Switch the load break switch into EARTH position with an
operation lever. As direct conversion into EARTH position
from ON position is impossible due to its mechanism that it
should be switched first to OFF position before the conversion
into EARTH position.
Only when load break switch is located at EARTH position
doors can be opened or closed.
In case any one of doors is opened, mechanism operation hole
is closed. Thus load break switch operation is impossible,
which means switching to ON position is not allowed
When the works such as replacement of fuse and cable repairs
are finished, all doors of fuse compartment, cable
compartment and cable test facility should be closed before
operation of LBS. The operation order to switch on is EARTH
→ OFF → ON.
Each door is to be pad-locked to avoid unintentional opening
that may cause accident
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
In single phase capacitor motor, if the motor rotate reverse direction then how much power will be consumed by the motor and why?
What type of wiring series or parallel is used for conventional and addressable type FAS & why?
What is time response of the control system?
why ht cable end termination don't have a gland?
is all the servo motors having brake?please specify which servo motors having brake for stop on position and which are not.
which cable is used for 15 Hp monoblock pump 3phase and service wire Distance is 210 feet please tell me cable size Armaured
WE know that for Inductor X=2pifL,In DC f=0,then X=0 so,V=IX=0;But In the DC excitation of rotor of AC generator,DC motor field coil which coils are inductor so why does not applying DC voltage short the rotor coil of AC generator and field coil of motor?If it would then DC source might be damaged but it is not happened. Why does the strand conductor of Electrical power transmission line make twist?
how can i find ct ratio of meter by seeing name plate of meter and how it should be used in MF calculation if it shows only-/1???
what are the difference between PLC and embedded
in non technical way how can u define POWER FACTOR??
Starting Time of LT & HT Motor
full form of electrical?
How do you select the pickup value of the relay?
can we use NPT glands in LT panel
any body,pls tell me how to done relay coordination ? how to coordinate by TCC curve?how to read the tcc curve?