we have LPG spherical Tank and we want to install DP Xmtr
for level measurement.below are the physical measurements
Total height of tank is 1850 mtr but 0% level is 1000mm
above bottom and 100% level is 450 below upper side.What is
the LRV and URV and please mention the formula .The SG of
LPG is 0.53 and Wet Leg method will be used.
Answer Posted / chinna babu
LRV=(1m * 0.53) -(18.5 m *0.53)
URV= (14 m * 0.53)- (18.5 m *0.53)
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What are the types of valves?
How u measure the massflow in orifice flow measurement techniques
why fuse block is not used for AI signal?
Can anybody please let me know Orifice plate sizing calculation formula and step by step procedure
how to measure draft pressure in transmitter pl. give its single line digram
what is exact time to study dcs and plc cources
what about your moleg in pogrees with company
i have been asked by QAFCO to appear for interview for thy post of Instrument Designer(INTOOLS)..i m engineering graduate with 5 years exp. in design engineering.Will this job profile suit me??i need all ur help n suggestions for thy same?
how u calibrate sox nox co2 co in cemps?what is opacity n HPm?tell the standard parameters of cems?
What are primary elements of measuring pressure?
what effects a surging can produce in the compressor
A PLC is programmed to drive three motors A, B and C as follows : After running motor A for an hour, motor B should get ON and motor A should get OFF. And after running motor B for an hour, motor C should get ON and motor B should get OFF. And after running motor C for an hour, motor A should get ON and motor C should get OFF. (That is, a cyclic repetition with time period one hour) Now, the second condition is: If any motor gone faulty and is tripped, the consecutive motor should get ON and the faulty (tripped) motor should be eliminated from cyclic repetition. The remaining two motors should bear the cyclic repetition of one hour each. (For healthy motor take logic as high and for tripped motor take logic as low) Now, the third condition is: When motor A load(Amps) exceeds 60% of its rated load, motor B should get ON in parallel to motor A. And when both motors A & B are running in parallel, and if their load exceeds 60% of their rated load, motor C should also start in parallel to A & B. [Here the cyclic repetition is eliminated, until their loads become normal(40%)] [Take logic high(1) for load at 60% and logic low(0) for load at 40%] Now draw a flow chart or a ladder diagram to fulfill the above condition.
what is a half wave, full wave, and bridge rectifer.
what is the procedure for auto tune in masoneialn 12300 series displacer type transmitter?
how can leve transmetter calibate in feild .and also put cv and flow plz .....