why transformer ratings in kva?

Answer Posted / chiya

kVA is the unit for apparent power. Apparent power consists
of active and reactive power. Active power is the share of
the apparent power which transmits energy from the source
(generator) to the user. Reactive power is the share of the
apparent power which represents a useless oscillation of
energy from the source to the user and back again. It
occurs when on account of some »inertia« in the system
there is a phase shift between voltage and current. This
means that the current does not change polarity synchronous
with the voltage. But the heat generated in a winding as
well as the eddy current losses generated in a transformer
core depend on the current only, regardless of whether it
aligns with the voltage or not. Therefore the heat is
always proportional to the square of the current amplitude,
irrespective of the phase angle (the shift between voltage
and current). So a transformer has to be rated (and
selected) by apparent power.

Is This Answer Correct ?    147 Yes 38 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How many types of losses occur in a transformer?

691


What is the function of a neutral reactor.

1310


what is a power factor?

1316


How to calculate earth wire load by formula

1961


LT cable fault chaecking equipment and to find out the distance at what distence it failure . Name and where it is available?

1668






WHAT IS THE USE OF PIG TAIL IN WINDOW CT ?

1912


what is the use of permanent magnet generator in exciter

1691


How could I get a certificate of competency as Electrical Supervisor? I have completed By BTech in Electrical this year(2012) for VJTI Mumbai Maharashtra. Is it compulsory to be produced while joining?

3004


USE OF 8 WAY PAN ASSEMBLY

1493


what is the use of commutator in dc motor if we supply ac ? commutator is used to convert ac to dc.and it is used to arrange the flux in unidirectional in case of dc supply. if we give ac as supply to dc motor what is the use of commutator?

1642


what is difference between 9kv 5ka surge arrester and 9kv 10ka surge arrester.

1404


How to calculat the ratio of HT\LT in energy meter

2124


th how could we differentiate between armoured copper and armoured aluminium cable what is the basic application? why we prefer the armoured copper as compared to armoured aluminium.

1462


Where should the lighting arrestor be placed in distribution lines?

662


what purose of the double circuit transmission line phase of the line phase changed for circuit-1 for Circuit-2 R-Y-B B-Y-R

1817