can we use 3 phase UPS for Motors and Other Machines

Answer Posted / engineered

Yes we can,
we have to ensure following things
1. In order to cope up with starting current of motor, we
have to select higher rating batteries, we can calculate
Idc required at starting of motor.
We have to refer battery current charts.

I have successfully run 3 nos. 7.5kw motor on 200kVA UPS

but when i tried to run single 7.5kW notor on 20 kVA ups it
failes to start.

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

In siemens S7-300 PLC, what is function and function block ? What is the difference between them ? When to use function and when to use function block ?

1649


what is apparent poewr, reactive power, & active power?

1735


TCS IS IT COMPANY THEN WHY DO THEY NEED ELECTRICAL &ELECTRONICS ENGINEERS?

1484


explain which quantities change in the starting and the and the running condition in induction motor

959


I want to ask that is there any relation between current denesity of copper and material purity. also is ther any standard which defines the standard current denesity of material.

1475






detailed procedure how we calculate cost for pcc m10 and rcc m20 including centering and labour excluding steel/ iron

2621


what is difference between earthingpits,earthing grid & earthing mess?

2062


send me all basic electrical question and answers

2536


how oltc works in rectiformers of higher rating (27 mva,200v dc,120kamps) please provide me full information with diaggram.

1725


how test transfomer(3 phase75kva) by megger

1622


Define ampere

713


Is there a standard depth of gravel fill in Substation Switchyard? Please give a design/drawing. Thank you.

4827


what is mean by kneepoint voltage? when it will happen? ( my doubt is, if CT secondary is open means ct get saturation or blas? what are factors are required for calculations? plz give currect anws:

1535


Write the force balance equation of m ideal mass element.

724


we have one oven for 12 zone we are installed ir lamp in oven we control load from thyrister and 0 to 5vdc so our zone no 8 getting bright in fraction of second so what we do.. Please answer

1304