Answer Posted / j jones
Sai Kiran.c is correct is saying that we don't start from 0mA because we need a "Live Zero" this is so that if the control loop goes open circuit we have an indication of this.
why do we use 4-20mA, not 1 or 2mA - 20mA, well simply just as in a pneumatic system we use 5-15psi, (0.2-1bar) it gives us the most linear output, and above that, if we were to use 1mA, any induced voltages from eddie currents in cables running alongside could cause a mA to be produced by the resistance of the cable, so our readings would be affected, and if we amplify the signal, the amplification has to be greater as we have to amplify 1mA more than a 4mA signal
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
how to rectify the poor signal strength in utrasonic digtial flow meter ,model:ge digital xce868i
1.what is the power consumption of three element drum level control in sugar industries? 2.how to reduce that?
What is the difference between modbus,fieldbus & profibus
What is offset in a control system.
what is the procedure to callibrate temp controller ,pressure controller,etc. suppose a temp controller showing error 1.5 degree centigrate how can i minimize it.
What is Predictive Maintenance
䑰ҕ䔈ҕ䖠ҕ䘰ҕ䛀ҕ䝐ҕ䟐ҕ䢐ҕ䥐ҕŹ
How to calibrate displacer type level transmitter (chemtrol make )for level measurement in hotwell , LP & HP heater ?
Explain the key components of control loop?
how to commission furnace ( water heater)
Draw a simple circuit for a well head control panel used to protect the well against fire, leak, blockage, ESD, & controls the operation of one downhole & one surface safety valve. Explain the operation and controls
can we create an interrupt in plc through scada?
How oil line flow measured?eplain about instruments used and working principle?
what is your eligibility criteria for freashers?
What is the use of GMV in turbine?