Answer Posted / ramadoss
Dear brother ,
digital earth tester containing of four
leads 1. C1
2. P1
3. P2
4. C2
C1 & P1 ARE LINKED WITH A WIRE AND THAT WIRE GOES TO EARTH
PIT ( wich you want to measure )
P-2 ARE CONNECTED TO SPICE ( ROD ) AND 10 MTR DISTANCE IT
SHOULD BE INSERTED
C-2 ARE CONNECTED TO THE SPICE ( ROD ) AND 15 MTR DISTANCE
IT SHOULD BE INSTERTED
AND ON THE DIGITAL EARTH TESTER AND SET THE VALUE IN 200 OHM
SIDE THERE WAS A BUTTON PUSH TO READ WE WANT TO PRESS
CONTUSIONALLY THEN SOME VALUE WAS SHOWN IN DISPLAY
fOR INDIGIUAL EARTH VALUE 1 OHM IS GOOD
FOR COMBINED EARTH VALUE 5 OHM IS GOOD
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
I Want randstand placement papers
Why squirrel cage motor can only use with low starting loads ?
Dear All we are having a problem in G120 BOP showing alarm A0503, F0052, F0060 we can not remove fault alarm ,Please any body help us. kowsar
Why L.T.Cable voltage rating is 1.1kV,where as system voltage is 0.415kV?
can the measured percentage error during calibration of single phase energy meter be negative?
Why is the air gap between the pole pieces and the armature kept very small?
what is the current setting for different relay protection for transformer .
How to calculate VCB rating for 33KV ,25 MW Power line?
why wire sizes are 3/29 or 7/29 and why not wire sizes are 2/29 or 6/29?
What are the raitings of Mcb,mccb and Acb in detail ??
Define the three phase formula fuse.
where reactive power is used
TYPE'S OF BREKAR ,WHAT IS TRANSFORMAR & SAFTY. STARTER DOL & STAR DELTA STARTER.
Why it is necessary to isolate fire fighting when you are taking shutdown for lv board.
how power trnafor from 1 point to another point in bus bar ya transmission line( voltage trnasfer from 1 point to another poin)