how digital four pin earth resistance tester works

Answer Posted / ramadoss

Dear brother ,
digital earth tester containing of four
leads 1. C1
2. P1
3. P2
4. C2
C1 & P1 ARE LINKED WITH A WIRE AND THAT WIRE GOES TO EARTH
PIT ( wich you want to measure )
P-2 ARE CONNECTED TO SPICE ( ROD ) AND 10 MTR DISTANCE IT
SHOULD BE INSERTED
C-2 ARE CONNECTED TO THE SPICE ( ROD ) AND 15 MTR DISTANCE
IT SHOULD BE INSTERTED

AND ON THE DIGITAL EARTH TESTER AND SET THE VALUE IN 200 OHM
SIDE THERE WAS A BUTTON PUSH TO READ WE WANT TO PRESS
CONTUSIONALLY THEN SOME VALUE WAS SHOWN IN DISPLAY

fOR INDIGIUAL EARTH VALUE 1 OHM IS GOOD
FOR COMBINED EARTH VALUE 5 OHM IS GOOD

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Explain about technical and non technical losses in distribution system?

627


state the working of discharge lamp?

1574


How isolater function when installed inelectrical 440V wiring

1708


i installed 100kva ups. what KVA genset they should provid in input side? plz any update formula or ans with reason.

1871


Why frame of the motor is specified?. If we mention KW and voltage level,automatically frame is decided or separately frame is compulsory to mention?.

1300






Approach of a cooling tower is the difference between temperatures of what factors?

620


How to calculate the copper in HT motors if KW, RPM & Voltage is given

2599


how we can set the IDMT relay.

1675


how generator avr give to the input?

1496


Define what is the function of anti-pumping in circuit breaker?

700


what kind of technical test that i need to learn because i have an interview tomorrow.. please someone help me..

1492


What are gain margin and phase margin?

836


please explain how to do 'pole drop test' on generator?

2386


Why neutral cable carry current.

1522


Why we are using only Dyn11 tranformer in distribution system but not using a Dyn1 in distributing system?why not and advantage and disadvantage in both

2320