A 60W,250V bulb when connected to a 230V supply will it give
more light or less or will be give normal light?
Answer Posted / idiot4ever
Resistance of the bulb element has to remain same for given
room temperature. so, for a resistive element like bulb,
P = (V^2) / R ; hence R = (V^2)/P.
The brightness depends on current and hence the power.
R remains constant. so ,
P (new) = P (old) * V(new)^2 / V(old) ^2
V (new) < V (old) , hence power output is reduced.
So it will be less bright.
| Is This Answer Correct ? | 17 Yes | 0 No |
Post New Answer View All Answers
Why only sinusoidal ac voltages are generated?why not triangular or sawtooth?
in HT service 3ph 4 wire service Y-phase voltage shows zero . whether it is meter fault? or what be the reason ? if y-ph voltage zero ,can current is recorded? reasons for failure?
how to calculate the loss tangent of electrical cables
Determine a suitable number of slors and conductors per slot for the starter 1 winding of a 3 phase, 3300 V. SO Hz 300 rpm alternator. The diameter is 2.3 m
1. What is differential relay? How it operates? 2.How to calculate the Short Circuit Impedance in Transformer? 3.What is the alternate solution for testing of polarity by using polarity tester while its milli ammeter does not works? 4. While testing the 33KV Busbar by using Hipot kit, what should be the test voltage we have to apply? 5. What is the procedure/activities to be taken to inject the current more than 2000A by using 2000A Loading Transformer? 6. Explain how you can give the overload setting to any Motor Protection Relay for a HT motors with formula and example? 7. Why restricted earth fault protection is needed? Why can’t differential Protection is sufficient? 8. What should be the minimum and maximum ohmic value for earthing? 9. Why DC Currents are not used in transformer? 10. What is the Frequency while we step up the voltage from 220V to 11KV? Is it possible? Explain it?
I want single line diagram for AMF & DG syncronizing panel
how many current required for hypo test
How to minimize the eddy current losses?
How to select, design,size & calculate for 11 KV/33KV/66KV/132KV/220 KV/440 KV circuit breaker for HT side of transformer protection/HT distribution protection?
why is the power generator connected as star earthed or star earthed through reactance and what its features ?
If one lamp connects between two phases it will glow or not?
Which test will be more severe for VCB?
Generator,motor and alternator Working principal Please explain easily
importance of reactive power management
What are two contours of nichols chart?