what happens to a turbo alternator if it get trip and 1 out
of 3 poles of circuit breaker in close condition
Answer Posted / a.p.nanjappa
Unbalanced current will develope till the upstream end
circuit breaker protection detect ( inverse time overcurent
and earth fault)and trips and isolate the fault.
The turbo alternator can run till negative sequence
charactristic constant limitation.I2t=K. Only generator
winding overheat and some time sparks,de[pends on fault.
It is also observed that major accident took place not only
damaging generator circcuit breaker pole damages,arcs and
body cabinet,arc chute burned,turbo alternater bearing
failure nted.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What it the purpose of parallel phasing transfomers??
What will happened if the neutral of the (star connected secondry) Xformer disconnected? (if its Above KVA rated one)
Define norton equivalent circuit?
Difference between drift current and diffusion current?
Explain the iniluencc of short circuit ratio on the pert'orniancc of synchronous machine.
What do you mean by pull of electromagnet?
what is the use of Auto re-closer?
Why 3 phase induction motor getting supply in body if one of it's phase is cut
what is the k var ratting of 1250kva
how desiel generate sart fail of eb?
Define rise time.
Dear sir, By which formula u can calculate for a particular kv line there is a range of mw.
Is there any relevant technique to produce power from light and heat energy of the sun simultaneosly from same rays of light?
What will be the diameter of pipe between conservation tank and transformer
How many types of protection relays are there based on the characteristic?