in 132 kv substation ligtning arrestor(120 kv) connected to
line. but line voltage comes to 132 kv, it operate or
not???
Answer Posted / avradeep das
In any conductor of 132 KV transmission line rated voltage
with respect to ground(remember LA is connected between one
conductor/phase and earth)is 76(approx) KV so 120 KV is
adequate
Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
What are the Return ( Monthly / quarterly/ Annual submitted to Electical Inspector for an establishment (Factory in Maharashtra-- Small scale category having seperate HT line of 22KV ) as per Maharashtra Electricity Act
The power factor of the fixed load is 0.8, now the p.f is varying from 0.8 to 0.5.
what is the voltages using in movie theaters??? why ??why not other??
What is a fuse? How does it work? What are materials used?
what is the reactive power what is the use of it in system
what are the interview question asked in wind mill about electrical
how to define tell me about self
low frequency protection why recomend?
why you don not show protection and type of isolation in key single line diagram?
Explain the experiment on ward leonard method of a speed control on a dc shunt motor with an suitable circuit diagram.
For a spring controlled governer the relation F = ar+b (F is the controlling force, r is the radius of rotation a and b are constants), indicates that the governer is
What is polar plot?
Is single load(eg: three phase motor) having all the components like positive,negative,zero sequence components during fault condition?
what are the differant std sizes of cable trenches?
we are having 110 Kv,250mA Electrostatic precipitators for coal fired boilers. what will be static voltage and current after discharge and what time it will remain before earthing?