in 132 kv substation ligtning arrestor(120 kv) connected to
line. but line voltage comes to 132 kv, it operate or
not???
Answer Posted / avradeep das
In any conductor of 132 KV transmission line rated voltage
with respect to ground(remember LA is connected between one
conductor/phase and earth)is 76(approx) KV so 120 KV is
adequate
| Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
What is the difference between circuit breaker and isolator
What is the previous name of Cox's Bazar
by using pump duty, how we will can calculate the motor duty(KW)? is there any standard or formula.
For overhead protection we use which transformer?
i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.
how to compute kvar in substation feeder to improve power factor and sending voltage
difference between Ac and Dc mcb ????
what is conductor constant of raccun conductor
What is force on parallel conductors ?
orifice sizing how done, checking & selection
Ceiling Fan and Storage type water heater. Discuss
what questions will be asked for 11/33KV licence interview APSEB hyderabad. Can any one share question and answers.
what is the use of static frequency converter and static excitation equipment? and where it is employed? for what?
how can we calculate the ratio of caustic soda and water in lrs.
what are the different methods for the starting of a synchronous motor.