what is the difference between high impedance REF & REF,
same high impedance differential protection & differential
protection for Power transformer?
Answer Posted / guest
REF protection can be implemented as High Imp or Low imp.
In high imp scheme, the CT ratios needs to be same but in
low the CT ratios may be different. Same is for the
differential protection. If the CT ratios are same the high
imp scheme can be implemneted as in busbar differential
protection.Key advantage of High imp tech is its immunity
to CT saturation . Key adv of low imp is to use CT with
different ratios for differentail / REF schemes.
| Is This Answer Correct ? | 10 Yes | 0 No |
Post New Answer View All Answers
What effect does a very low impedance have on the Voltage regulation? On the short-circuit current?
What is the name of the winding from which the supply is taken for load connections?
Which type of a.c motor is used in the fan (ceiling fan, exhaust fan, pedestal fan, bracket fan etc) which are find in the houses ?
What is the Current equation in series RLC circuits.
why ht cable end termination don't have a gland?
Greeting to all members, How to calculate spill current when we have different ratio CT and Class for REF(Low Imp) I have 500/1A 5P20 @line side n 400/1A CL.X @ Neutral.
A Question Like A Wire Is Wound Whose Resistance Is Some 132. 44647 Ohms. If A Voltage Of 30 mv, 296 Ma Current Is Applied To It What Is The Resistance.
hi , i have 150 kw loud and we need 50 m cabil,i want to know wich size cabil we use. thanks
Whats the minimum value for I.R. that can be allowed for HT & LT alternators for operation?
what is Anti-pumping?
what is mean by PIR in circuitbreaker and give me detail of that?
please send previous exams question papers
what is the difference between Central Battery System and UPS in applications and uses? and why UPS suitable for Computers and central battery for emergency lighting?
Draw a circuit diagram in which if button is open we can use socket and bulb as a series test circit and if button is close than simple we can use socket as any load purpose.
can some one clearly explain why -48 volt DC use in telecom site????