how to choose the cable rating for load (KW)? EXAMPLE.50KW load
Answer Posted / sunil patil
Given- KW-50
Now from formula I= KW X1000/(V X I X 1.732 X .8)
=86.95 A
Now by refering fenolex cable rating table
For 25mm2 =80A Which is less than our o/p current so we
can select 35mm2 having current capacity is 102A
| Is This Answer Correct ? | 36 Yes | 12 No |