when 40 watts and 60 watts bulb is connected in series,
which bulb glows brightly ?

Answer Posted / wareagle

Ksb Quote "40 wattbulb has higher resistance(1440) so a
low current pass through it but 60 watt has low resistance
it glows brightly" That would be true if the bulbs are
connected in parallel but they are connected in series.
Read the question. Do you know what that means?

Ksbn That is incorrect. Lets find the answer.
Voltage = 240 volts
Watts = 40 watt and 60 watts
R60 = 240x240/60= 960 ohms
R40 = 240x240/40= 1440 ohms
Total of R60 + R40 = 960 + 1440 = 2400 ohms for series ckt
Amps = 240/2400 = 0.10 amps flowing thru both 40w and 60w
watts = amp²x R
watts for 60 watt = amp²x R = 0.10² x 960 = 0.01 x 960 =
9.6 watts
watts for 40 watt = amp²x R = 0.10² x 1440 = 14.4 watts
Therefore 40 watt is brighter.
Remember the bulbs are connected in series not parallel.

Is This Answer Correct ?    38 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is an Air COmpressor

1727


if two transformers are placed parallel & both have fault impedance of 50KA will it increase or decrease show example?

1540


gas turbine genrator reactances

1527


What is the comparison of PILC and XLPE cable

1511


How can i calculate the Breaking capacity of molded case circuit breaker, is the breaking capacity of CB for Diesel generator shall be less than grid supply's breaker ?

1713






what is meaning of bus riser

1957


what is the min and max ohmic resistance for the earthing rod installed for lighting poles for street light network

3039


why starting current is high and resistance is almost 0 during the starting of motor dc motor...?

1287


why swinburnes test cannot be performed on series machines?explain

1840


what is power factor ? how we can calculate the low power factor and amount of capacitor for improve that low factor ?

1094


Would you recommend to replace all oil filled cables with xlpe cable for hv transmission with the current technolgy for xlpe cable?

1064


what is the function of gss in the dg set.

1481


ASTM D 3455 - Standard Test Methods for Compatibility of Construction Material with Electrical Insulating Oil of Petroleum Origin has been used for Testing Transformer Oils with a product placed in it. Aged Control Oil has a Power Factor of 0.032% at 100°C. Aged Oil with a Test component has a Power Factor of 0.093% at 100°. Is this increase acceptable? If not why? How much increase is acceptable?

1519


How do we calculate the resistance per metre of single core aluminium stranded cable 19*3.25mm sheathed in pvc,at 15 deg C temperature?

1946


What are the limitations of Kirchoff's laws?

1128