Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is ten delta ?

Answer Posted / amit shankar choudhary

Tan Delta, also called Loss Angle or Dissipation Factor
testing, is a diagnostic method of testing
cables to determine the quality of the cable insulation.
This is done to try to predict the
remaining life expectancy and in order to prioritize cable
replacement and/or injection. It is also
useful for determining what other tests may be worthwhile.
How Does It Work?
If the insulation of a cable is free from defects, like
water trees, electrical trees, moisture and air
pockets, etc., the cable approaches the properties of a
perfect capacitor. It is very similar to a
parallel plate capacitor with the conductor and the neutral
being the two plates separated by the
insulation material.
In a perfect capacitor, the voltage and current are phase
shifted 90 degrees and the current
through the insulation is capacitive. If there are
impurities in the insulation, like those mentioned
above, the resistance of the insulation decreases, resulting
in an increase in resistive current
through the insulation. It is no longer a perfect capacitor.
The current and voltage will no longer
be shifted 90 degrees. It will be something less than 90
degrees. The extent to which the phase
shift is less than 90 degrees is indicative of the level of
insulation contamination, hence
quality/reliability. This “Loss Angle” is measured and analyzed.

Is This Answer Correct ?    4 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Can a generator runs after getting 1st stator earth fault.

1357


prove that power consumed in 3 phase delta system is 3 times as compared to 3 phase star system

2158


What is the function of capacitor in electrical circuits?

987


PLEASE ANYBODY HAVE ELECTRICAL CIRCUIT DIAGRAM FOR CHMER PULSE CD 60M SPARKING MACHINE.PLEASE MAIL ME SUPRIYAAYYAPPAN@YAHOO.CO.IN.

2749


HOW TO DESIGN THE body EARTH cable(Copper Conductor) size for 60KVA UPS?

1948


Why are iron cores in transformers made laminated?

1049


cc of scorpio?

2232


distribution transformer de-rating formula on over limit iron losses  

2242


why current is constant on d.c?

2033


Did RMU have ct and pt ?

1313


how to decide the panel size like MDB ,SMDB PANEL SIZES

7293


How we calculate the Multiplying Factor of Kwh meter for 3 phase alternator.

1834


why starting current is high and resistance is almost 0 during the starting of motor dc motor...?

1685


What is the method for testing the differential protection stabilty in generator? When the time of starting What will happen if differentail protection connection wrong means?

2229


Please brief me about number of pole in alternator.In single phase alternator coils are connected in star or series. How to calculate frequency for the same.

1854