The transformer which is smallest in size is and how to
calculate that? The options are
100 KVA, 50 Hz
100 KVa, 100 Hz
100 KVA, 25 Hz
50KVA, 25 HZ
Answer Posted / wareagle
The transformer equation
E = 4.44(f)(B)(N)(a) where E is the voltage in the winding
either primary or secondary, f is the frequency, B is the
flux density in the core, N are the number of turns on the
winding, and a is the cross area of the core. At higher
frequencies the number of winding turns N is reduced. This
formula follows from the Faraday formula, E = N dθ/dt and θ
= B(a).
This formula is why switching power supplies use a much
higher frequency (thousands of hertz) than 60 hertz, they
use smaller transformers that don't need as much wire as
transformers operating at 60 hertz. See Wikipedia for the
transformer website:
http://en.wikipedia.org/wiki/Transformer
Source(s):
Wikipedia for the transformer equation
100 kva 100 hz
| Is This Answer Correct ? | 9 Yes | 1 No |
Post New Answer View All Answers
can i use the six sigma method which is used in management area, in state estimation of power systems?
if voltage bt phase & nutral is 38v in a panel board . whats the root cause.
TYPE'S OF BREKAR ,WHAT IS TRANSFORMAR & SAFTY. STARTER DOL & STAR DELTA STARTER.
The electromagnetic torque developed is proportional to what in a D.C series motor?
what are the differant std sizes of cable trenches?
What is George phenomena to start the synchronus machine?
how to test power transformer.YNd11
how we can find of current direction(supply comming/out going direction) when a transmission line passing through sides.
hi....I am from india..i have completed my engineering in electrical and electronics field with 58.4% and my IELTS score is 5.5 bands....Recently i received my I-20 in computer and information science from Troy university in Alabama.On 18th i have a visa interview can u please tell me what type of questions i have to answer ??????
how to find the multiplication factor for digital energy meter and analog energy meter
In 11/0.414 KV Parralel supply network with Bus tie closed what will be the fault level is it doubled or halved??
what are the components in electrical control panel (for example: 415V, 3-ph, panel to operate utility and 3-ph DG set).
Why L.T.Cable voltage rating is 1.1kV,where as system voltage is 0.415kV?
From past few months I am getting lagging pf even though sufficient capacitors used in circuit. Where is the problem pls answer
The SFC of an engine is 0.25 kg/kW hr. when the fuel used has a calorific value of 36000 kJ/kg. the thermal efficiency of the engine is