HI FRIENDS IHAVE QUESTION 1.WHAT IS PARTIALSTROKE TEST?WHY
IT IS USED ON ESD ON OFF VALVES?
Answer Posted / sebastian
ESD valve or EIV(Emergency Isolation valves) are only used
(operates)for Emergency conditions only, usually theses
valves are reamins open till incase any Emergency occures
that is fire .some times it remains open till plant next
turnaround@3-4 years).so valve trim or actuator may stuck
due to some reason and valve never clos when real
Emergency, to avoid this situation , goverment athority or
insurance company guidlines are given to plant operation
section to check availablity and functionality of ESD
valves periodically, may be each 3 month, 6 month etc.
Partial stroke: Valve start to move from its open position
to close postion only @20-25% of its total traval(to avoid
process upest)and return back.there is a Function logic
built in the ESD logic with Protection timer(incase valve
limit switch not moved from open postion at set time the
logic will re set for valve its open condition and
indicate failed.(partial stroke test failed) .
if valve moved from open position (by means of limt switch
leves its contact)logic will re set and remais for open
position and indicate succes test.
if any details requred with logic contact me
sebalukose@gmail.com
Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
what is performance test.need defination
why would you like to join our company
Make a ladder diagram on LSL valve will close, on PSL valve will open and start the motor
what is the current pay package for an instrumentation engineer having 2 years of experience in cryogenic technology???????
can you send remote seal interface level transmitter calculation steps for oil water saperator.
For crude application in floating roof tank, how to calibrate a DP Transmitter? How is the floating roof weight considered?
What is shielding effect?
We are using Rosemount 5400 series Radar Level Transmitters in all types of Sump Applications having oily water hdrocarbon petrochemical nature. What we are facing the problem frequently is that always getting reading frezzed at some value. If we do power recycling , sometimes it is working . then making same freezing problem. If anybody faced before such type of problem and also having solution , Please give the answer.
What is Positive Calibration and Negative Calibration?
Where Can i take a SPI INtools training in Mumbai? In Rolta India Ltd to whom I should approach regarding of SPI INtools Training?
why we use the ac supply load cell>?can we use the dc supply load cell?advantages and disadvantage of the ac supply load cell?
Hi Friends i need Electronics&Instrumentation Engg question papers for BARC written test by coming 20th May 2008 pls post ur use full info to kkumarei@gmail.com. Or for suggestions pls give one missed call to 9962122264
How to check vortex flow meter is in good condition while we do not having calibration setup?
Hook up resistance decade box to temp.transmitter.
it is possible to check the fail safe condition in pressure transmitter. if possible how?