Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the difference between the 94 lockout relay and 86
lock out relay. I have noticed that the 94 lockout relay is
activated when the distance realy is activated and 86 is
activated when the 87T differential is activated. but why
can't the same lockouts be used for both the protection
schemes

Answer Posted / sachidananda pal

86 is actually an Electrically/Hand reset Master trip relay
that trips both the primary & Secondary of a Transformer
whereas 94 is a lockout relay that is used in transmission
line protection eg. in an Auto recloser.In case of a fault
the Autorecloser shall start it's O-t-CO-T-CO-T-CO-T-CO
operation. After un successfuly trying to reclose the line,
the 94 Lockout relay shall act afetr the time duration set
& will put the Autorecloser in an Lockout condition so that
there are no further reclosing attempts.

Is This Answer Correct ?    3 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

can anybody send me syllabus of rrb section engg (electrical). and also send previous question pepar...

2041


how to calculate earth fault relay current and CBCT ratio

8401


the grid connection required for a 50 MegaWatt fotovoltaic powerplant is higher or lower than 35kv (high or medium tension)?

1904


PLEASE SEND ME NTPC RELATED INFORMATION LIKE WHICH TOPICS HAV MORE SCOPE,BOOKS TO READ,CUT OFF...PLEASE.mail at thiru.1203@gmail.com

2153


What is method of calculating the fault current for a MDB, 50KW, 3PH, 415V, 50HZ?

2180


Who many reason of ignition fail ?

2014


derive DC RMS value for half wave rectifier?

3243


in parallel operation of power transformer why the distance between power transformer and capacitor bank feeder is necessary to know

1857


Why in ESP Positive earthed

3148


How to Calculate the Fault Level of Electrical Installation

2309


what size steel armoured cable is required to support 1500kva capacity. would 70mm squared be enough or would I need 90 or 120mm squared 3c plus earth

1431


DC transmission

2134


What is power distribution criteria for converting single phase unbalanced residential load to 3 phase star connected balance system. Does total KW converted to 3 Phase. Means Divided by root 3.

2393


What can you contribute to the progress of our Company as an employee if you are selected?

5472


Whats the minimum value for I.R. that can be allowed for HT & LT alternators for operation?

4147