Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What will be the average KVA rating of Auto Transformer
for 75kw 415V , 3phase induction motor

Answer Posted / arulkumaran

POWER FACTOR = 0.85 (APP)
KVA = KW/PF
KVA = 75/0.85
KVA = 88.235
SO,average kva of auto transformer 90KVA (APP)

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to find number of run cable laying[LT side] for transformer & alternator secondary side? [above condition for getting output power transformer to main panel side] give the example.

2016


Can we use Ccapacitive voltage transformer directly for metering purpose?

1784


Hi Suppose we have a wye/wye transformer which is grounded at both sides,in this situation, do we have ay ground transformer? in other words, ground transformer can do any thing more (while we have nuetral wire in both sides)? As the last question, what about 3rd harmonic? we have two choices: first using wye/delta transformer + ground transformer and second using wye/wye earthed connection.in the former choice, we dont have 3rd harmoonic at the secondary side but what about Yn/yn conection? do we suffer from 3rd harmonic in the Yn/yn connection?

1912


How much load can take a 16 mm aluminum cable 3 phase

1700


What is mean by STUB protection?

1999


how u measure/calculate renge of capacitor,capacitor has no any rating tag.what is the theory of measure of capacitons.

1933


What fomula is used to calculate: 1. rated frequency withstand voltage, and 2. rated lightning impulse withstand voltage.

1666


My load is 1635 KW. & current pf is 0.884, I have to improve it for 0.99.Please suggest what KVAR value is needed?

1554


how to calculate the distance relay faulty zone?pls explain?

2006


please send 5yearje solved papers on my email himmatsinghnathawat@gmail.com

1871


what are the industrail measures to over ferranti effect? how would the ferranti effect the power system if those remedial mearsure arent taken? how often does this effect occurs in real power system?

2086


What is the restart inhabit setting in ABB spam150c relay (Motor protection relay)

3587


what is mean by dry frequency

2404


Define Electrical Insulation and examples of Solid,Liquid and Gaseous insulating materials?

1708


what size steel armoured cable is required to support 1500kva capacity. would 70mm squared be enough or would I need 90 or 120mm squared 3c plus earth

1338