Im designing APFCR Panel for 600 KVAR.I need to calculate
the full current so that i can choose the capacity of
isolator/Breaker.Kindly suggest with formula.
Answer Posted / wareagle
600 kvar/kv x 1.73 So if the voltage = 400 volts the
amperage = 600/0.40 x 1.73 = 867 amps. Your breaker would
be determined by your local code. USA would be
867 x 1.35 = 1170 or a 1200 amp breaker.
| Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
What are locations arc protection relay is fixed.
I have a reading off 1.5ohms at my mem my main c/b is rated at 40/6 amps in a domestic house and i was told to change it to a b curve c/b is this ok
how to ctrl motor by use of ac or dc drive.plz explain evdintly
Alternator rotor earth fault relay circuit
What are IR values and what it should be for coil and for insulator
Which type of air compressor is used now a days in the market. Keeping in mind of energy efficiency and maintenance points. Relevant documents may also be sent on mentioned email ids.
iam preparing for rrb section engineer post in electrical branch.suggest the right textbook for my reference.fromwhere i will get the previous q.papers?
We have a couple of oil tanks at our plant. One of them does not have a lightning arrester installed. My question is it necessary to install an arrestor on every tank or will this particular one be covered by the arrestor installed on the ajdacent tank, Since all the tanks are close to each other. Basically, I want to know that if these arrestors or protection works in a parituclar area of effect or influence. Thanks
What is power relay?
what is a types of short circuit and what is a types of distance protection tests
what is the basic need of domestic loads 1- voltage 2- current
How to calculate the multiplying factor for energy meter with ct ratio given
how to select energy meter? have any calculation?
How much current will a 5 HP delta connected motor at no load will take?Is tat need a starter
A powerplant has 8 gensets operating in grid parallel mode. In one genset sometimes there is pf variation and kvar variation. The plant operates in pf mode. When this variation is observed the load is stable, voltage is also stable, freq and genset speed is also stable. How will you check the functioning of pf card. What shall be the ideal output vdc of the pfc, from there it is input to AVR?