How to select Main CB Rating for 220 KW Load?
Answer Posted / ashif khan
before the selection,first we should know that it is single
phase or three phase load.in case 1-phase we use p=vicosф to
find out the load current but in 3-phase we use p=√3vicosф.
suppose it's 3-phase then load current=382amp.now add
minimum 25% safety factor to it.then it will be 475amp ,so
we can select C.B of 500amp current rating.
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
hi frnds...pls send me aptransco previous papers .....pls..pls,,,(madhar.rocking@gmail.com)and suggest me some websites
if i am in front of transmission line how to know that current direction without any equipment
In HVDC LINE RECTIFIER CONTROL ON CONSTANT CURRENT AND INVERTER CONTROL CONSTANT EXITATION ANGLE CONTROL BUT HOW INVERTER CONTROL CONSTANT CURRENT?
A jet of fluid strikes a plate What was the force required to counter it?
Why you want to join non technical field when you are an engineer?
What is the need of earthing transformer for delta side of a transformer. (Think of a line section between a star/delta transformer at a grid substation and delta/star transformer at a village. An earthing transformer is there at the delta side of the star/delta transformer at grid substation). As there are no ground reference there will not be fault current if a one phase is grounded. Further L-L phase will be sensed by the primary side of star/delta transformer as a L-G fault. So why an earthing transformer is required at delta side
Saving in copper achieved by converting a 2 winding transformer in to an auto transformer is determined by A voltage transformation ratio B load on secondary C quality of core material D size of transformer core
which pump used in WTP explain the function of VFD how to dtermine capacitorbank of capacity one plant
Why power factor should not be in leading (capacitive) mode of any load.
what ispositive, negative, zero sequence impedence?
what will happen reduce the transformer voltage from 415v to 406v, is it save the energy,? are this methodis good to reduce the energy.?
If one tertiary phase i.e. R,Y or B is earthed of a loaded type tertiary delta connected (Without load)of a power auto transformer, what is its advantage/disadvantage?
How to select a contactor? How many types of contactors are available
Why does increasing the magnetic flux in the main field of a d.c motor cause the armature current to reduce??
defination of controlled shunt reactor