Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what do you mean by PF correction. A motor is rated at 15
kw,415 volts, 0.7 pf and eff of 0.92. The powerfactor is
improved to 0.98 by adding capacitors at the bus. calculate
the current drawn by motor under full load condition before
and after pf correction

Answer Posted / gk

Full load condition means rated power of 15 kw
condition.And P=VICOSQ. where v assumed to be maintained at
415v from terminal.So ICOSQ is constant to maintain rated
15kw(= (V)*(ICOSQ)) full load. Therefore if PF is improved,
current drawn by motor from supply mains will be reduced.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How we can calculate the consumption in kwh of motor on basis of kw @100% load, @50% load & @ no load.

2796


What is minimum phase system?

1143


I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?

1888


Can any answer me ,What will be the range of C.T coil for L&T energy meter EM301 used for 180 kva DG set

2199


Difference between ac parallel circuit and ac series circuit?

2117


what is d check in dg 1500kva

2125


i need the details about bhel exam.how to apply for that.please send to my email-id.thenmozhi2k7@gmail.com

2014


What is the use of iron core in a transformer?

1137


Air refrigeration cycle works on the

1100


66kv under ground cable how to layaing in ground any special case two ckt r runing

1997


If 100 KAV USP dedicated earth got disconnect / Cut. What will happen at load.

1971


How to Prepare preventive maintenance shedule of machine tool.

2021


What happened when voltage will half value of current ...

1615


in a simple IDMT relay we use neutral point of ct for earth fault then what is the requirement of neutral ct and cbct?

2165


DG Earth Value?

2311