what is the function and use of oil filled cables specify
its advantages and disadvantages
Answer Posted / jason008
oil filled cables are not like transformers as there are no
cooling towers for the oil to be circulated around
adv of oil or fluid filled cable. 1 Longer service life you
can mointor what is happening inside the cable you know if
a 3rd party has slightly hit the cable as you a low
pressure alarm goes off less dielectic losses smaller
conductor size for same ammount of current for xlpe see ppl
oil filled cable they have been used for many years
disav higher cost takes longer to join lead sheath of older
cables leak.. this has been improved by alum sheath
Xlpe adv cheaper less maintenance.
xlpe disadantages unable to see when the cable is going to
fail no pre warning water can migrate into xlpe greater
losses in xlpe you can not test the xlpe in the same manner
as oil cable satuation test which test stress cones ect its
the earlier joint where very hard to do.there are to many
variation of joints between diffrent companies
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
For electrical designers what are the standard should know? i want learn about this standards. how to get information/reference. anybody help in this regards please.
In general bus riser follows the bus section in SWGR. What are impacts if bus section follows bus riser?
What are the weight of 800KV DA,DB and DC type tower ?
What would cause a 240v choke that should give 110v out on a 16w lamp to gradually increase to 160v?
How to select the proper VSD to operate high inertial load
Define branch?
how to find the torque of the single phase synchronous motor by doing an experiment
PLS SEND THE RRB CHENNAI MODEL QUESTION PAPER my email id is ganesan98655@rediffmail.com
How Load Factor, Demand Factor, Diversity Factor etc best applied in designing an electrical circuit? Is it allowed to consider these factors in each and every panel in an electrical distribution system? Can any body suggest a good book for reference?
How will polarity test of Dy5 Transformer ?
I just purchased a 4 position cam switch to be used to operate a 3-speed blower motor. The motor is a 10 amp motor and has 3 wires that are used to control speed. The cam switch was rated at 660V 20 amps but when I received it, I noticed that it has AC-15 operational current rating (Ie) of 4/5 amps. If I am reading the label correctly. the 4/5 amps is related to 440v/220V (Ue). Other ratings are AC-3: 5.5A, AC2: 7.5A and AC-4: 1.5A. My questions are 1) Is it safe to use this switch with the motor I have 2) what is the difference between the 20 amp Ith ratting and the Ie operational ratings?
Why do power lines not short out when they fall into water?
iam using DM 3251 voltmeter(1 percent accuracy)for 11KV system PT ratio is 11KV/110V.can anybody explain what is the max and min voltage deviation.
How can we connect additional batteries to three phase ups? What are parameters we have to check when connecting?
hello!my name is sheikh iam preparing for indian engineering servieces,please send me the old question papers..to sheikhshaazforjobs@gmail.com