Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Are same transformer be employed for step up and step down
services?

Answer Posted / bajrang ahirwar

NO
same transformer can't be used for both operations.
exception is ICT like 220KV/400KV
ICT is inter connecting or interposing transformer, these type of transformers are specially designed.
there no load an on load losses ane calculated so that they can be operated from either side.

on the other hand if have a 2000 KVA 11kv/440V 0.85 pf step down transformer:
current in hv side will be = 123 A
and current in LV side will be =3087 A


the secondary has to bear heavy current so it is designed accordingly with Thick winding.
and HV Primary has to carry a comperatively low current so its windings are of thin windings.

NOW the reverse operation

the heavy winding will be connected to high Voltage 11 Kv side, fine no problem, because it has to carry a lower current of 123 A ans secondary is rated for 3500 A approx.

BUT
the thin wired high voltage winding will now have to supplly the larger gurrent 3080 A, this winding has also larger losses R=Rho L/A
result??
the winding will burn out.

so practically it is not possible.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What effect does a very low impedance have on the Voltage regulation? On the short-circuit current?

6289


Why colled 440V to 3-phase supply.

2142


how to calculate the surge level of surge suppressors related to the SF6 cicuit breakers?

1962


What are the advantages of autotransformer?

1212


Which device of PlC does share load between DG sets when DG are running in perallel?

2062


what type of earthing do for dry fissure rock?

2429


When we connect the large capacitor bank in series ?

1088


how to wiring it with contactor and timer together

1828


are there rmu for 3 transformer?

1870


A mass of 1200g is accelerated at 200 cm/s2by a force. The value of the force required is:(a) 2.4N(b) 2400N(c) 240 kN(d) 0.24N

2963


What is the different between conventional MCC and intelligent MCC? Common controller or controller for each bucket

1065


HOW WE CALCULATE CURRENT IF THERE ARE NOT PRESENT ANY AMMETER OR MULTIMMETER??????

1850


why we permissive overreach in distance protection.where it is applicable to use in long r short lines

2758


What shall be the secondary output voltage if the primary winding of a 220/6V, 50 Hz transformer is energized by an 110V, 60 Hz supply?

1363


What happens to a line-frequency of high-frequency transformer when it is first energized/ re-energize?

2150