What is fuction of NGT/NGR using in Generator.

Answer Posted / sunil

NGR basically used for Star connected Generator. It is
basically limit the fault current and protect the
generator.Its value is calculated with the help of Generator
Core caring capability curve i.e. at what Amp you restrict to
flow in core. suppose you restrict 100A current and your
Generation voltage is 11 KV. then at the time of fault,
Voltage applied across the NGR is 6.35 KV. and with the help
of this voltage, Resistance will be V/I which is 63.50 ohms.
At the time of fault, normally Earth fault (Sensitive/stand
by)operated. and in case they not operated then current
having magnitude more than 100A will burn the resistance. and
system become unearth i.e. system will isolate from earth.

Is This Answer Correct ?    25 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is lighting kitts.

1832


Mention what are the types of semi-conductors?

934


Ceiling Fan and Storage type water heater. Discuss

1744


can we do the star delta connection of capacitor for 3- phase motor starter.

1798


Greeting to all members, How to calculate spill current when we have different ratio CT and Class for REF(Low Imp) I have 500/1A 5P20 @line side n 400/1A CL.X @ Neutral.

2754


Why i receive the GCU fault in my DG Sychronization panel . what all the factors considered for this fault .

1966


what is subtransient , transient and steady stateac components

1921


How to calculate capacitor bank size at a load 800kVA.

1374


Why IR value of the (HT cable Plus synchronous motor) is less while individually having IR values in GΩ?

1550


What is a system?

884


What is the difference between Generator Differential Relay and Transformer Differential Relay?

1952


What is the vector group of a transformer,how can it be found out?

1787


How I calculate the ELCB for circuit breakers?

1896


WHY TERTIARY OF POWER TRANSFORMERS IS LOADED WITH EQUIPMENTS LIKE CT,PT,ISOLATOR AND CB

1665


what should be the no load current for 3 phase ac motors ranging from 5 kw to 1000kw?

1572