an off load but energized 11/0.4 KV, 1250 KVA T/F has a
power factor of 0.65(capacitive)..!! why is it so, though
T/F being an inductive device ??
Answer Posted / rajesh verma
Dear
It is not possible. As the transformer is a inductive
device it can only lead to Lagging PF although it is idle
but there was definitely Lag PF the one possibility is that
the transformer is feeding to capacitor panel and because
it is off load so the resulting PF is Leading second thing
can happened that PF relay not working in auto made and
somebody has connected direct capacitor without calculating
the required KVAR to maintain transformer off load PF
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
How can we find out LT UG cable fault (size,from-4*25mm sqr to 4*300mm sqr)? How mani types UG cable faults?
How we calculat the NGR of 3phase Generator, Our generation voltage 11KV
what is formula for zero phase sequence of nuetal earthing transformer of 6.6 kv
How many points does a Circuit can have?
What are the main advantages of generalized error co-efficients?
Why is ignitor used in sodium vapour lamp
What is the important precuations need tocarried out while working with Electrolite in Battery PM?
What's mean HVF & HAF in Vacuum Circuit Breaker?
what is the effect of back reactive power on the generator ?
what is the difference between ac motor and dc generator
Differentiate between low pass, high pass and band pass filter?
Best way to measure the Soil resistance of rocky soil, three probe method and four probe method
What is a DC series motor?
What is cable tray, its type, and its support?
Merits & Demarits of Oil circuit & Air circuit breakers ?