an off load but energized 11/0.4 KV, 1250 KVA T/F has a
power factor of 0.65(capacitive)..!! why is it so, though
T/F being an inductive device ??
Answer Posted / rajesh verma
Dear
It is not possible. As the transformer is a inductive
device it can only lead to Lagging PF although it is idle
but there was definitely Lag PF the one possibility is that
the transformer is feeding to capacitor panel and because
it is off load so the resulting PF is Leading second thing
can happened that PF relay not working in auto made and
somebody has connected direct capacitor without calculating
the required KVAR to maintain transformer off load PF
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
operation of protection relay watchdog contact?
If we need4× 50mm sq cable but it's not available so we can pull 4×25mm sq 2cables
What is q factor?
if a.c supply is given to the motor,, what happen?
If the feeder rating is 7.5 kw or 10 HP star-delta feeder, MCCB is taken as 63 a, contactors-32 a, how much will be the OLR rating or which range OLR should be considered when we concern about type-2 coordination?
What are the advantages and disadvantages of negative feed back?
1hp= how much rpm
Why control of DC motor is simpler?
what is the breaking capacity and making capacity of circuit breaker and how
a 230v transformer with step down ratio 19:1.it has 2000turns on primary and rated 25va calculate max primary current no of secondary turns volts/turn
why h parameter are called as hybrid parameter?
How u can give the overload setting to any motor protection relay for a HT motors with formula and Example?
what is the disadvantages of common earthing for AC and DC equipment? (i am talking about inverter control room and inverter duty transformer earthing is common...?)
in science exhibition how lamp can blink when you clap near the lamp ? thank you
When semiconductor fuse does save thyristor in each cycle of conduction? Why under voltage setting keep less in SPRS and more in DC drive?