How much current will a 5 HP delta connected motor at no
load will take?Is tat need a starter
Answer Posted / asif.k64@hotmail.com
1HP=746watt
5HP= 3730watt
power = 1.732*v*I*cos@ for three phase motors.
I=3730/1.732*415*.8
I=6.5A
Hence the motor will draw a no load current approximately
about 6.5 A.
There is a need of a starter.
| Is This Answer Correct ? | 13 Yes | 3 No |
Post New Answer View All Answers
What will happen if we introduce negative feedback to a control system that uses a positive feedback?
am commissioning the trafo without connecting the neutral therefore unbalance will occur what is the alternative solution for this?
what is thresold of perception
before synchronizing an alternator,power factor is leading ,why?
why incomer bay is required before transformer bay if there are more than 1 nos. of transformer bay.
which IS or IEC is used for earthing,breakdown voltage of transformer oil, hv/pd testing and all type of electrical testing
hi there i am highly enthusiastic about discussing electrical concepts , and hence i wud lyk to invit al do intrested to join me at gtalk and hav a dscussun of the concepts , ad me as a freind . my email id is rakesh.2k99@gmail.com
ow can i get certificate of competency as electrical supervisor and my diploma in electrical engineering from jalgaon.
Dear all, I'm manikandan I have done by DIPLOMA EEE from 2011 , I have 5 years of experience from Power plant instrumentation field , which one field is give long life & which one field is best ,I confused a lot and also I'm studying AMIE, can I choose which department from Section B examination? pls tell me
In case of generator when we consume more power produces by it why load on generator increase and starts sound more. and how it is adjusted..
application s to shunt coil
what's prime importance of protection in electrical system.if protection system don't work properly what can happen in electrical system?
How stabilizer works??
Alternator rotor earth fault relay circuit
Transmission voltage is kept 11KV,33KV,66KV,132KV,220KV due to form factor. What happen to 400KV and 765KV transmission voltage?