A pressure differential gauge type of instrument has a
manifold with 2 isolation valves (hp and lp),2 vents(1 each
for hp and lp) and 1 equalizing valve. Determine the
position of each valve(either fully closed or fully open)
when troboulshooting to:
1. zero the transmitter.
2. determine if there is a block in the impulse line.
3. determine if the gauge is functioning properly.
The process fluid is water.
Answer Posted / abinecious
If u close both hp and lp isolation valves and open the equalizing valve u'll get zero reading means the gauge ll working properly and also u came to know zero output is also true. if any block is there means the gauge r transmitter shows full scale reading.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
How can you add value to this Industry if offered the job?
what is the criteria to decide conductor size of a cable ?
How can we use feedback signal frm rtd for monitoring and in dcs for controlling ,then which type of rtd is sutaible 2 , 3,4wire and why ?
what different types of problems do occur while doing instrumentation commisioning and how to solve them? please explain in detail
SOME OF YOUR QUESTIONS ARE NOT MAKING ANY SENSE SO TRY AND PUT IN A LITTLE BIT MORE EFFORT BEFORE YOU POST A QUESTION. WE WILL ONLY HELP THOSE WHO WE CAN SEE ARE TRYING TO HELP THEMSELVES.
how to change measuring units from mmwc to cubm/h in rosemount air flow transmitter with hart communicator fluke 744
need instrumentation job completed 1 year trainee ship in mnc pesticide company. now in search of job
What are different types of control valves?
What is instrumentation technologists and mechanics?
What is the formula of vabration sesore. i mean how to covert mils to volt plz share if any body knows very argent : my mai is merajalam143545@yahoo.com
any body please send me the old question papers of ongc test.
control panel design guidelines
Explain the mechanism behind the turbine meter.
what is cems analyzer explain with principle and drawing ?
what is the input of digital counter during the the calibration time?