Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How instantanious short circuit current is calculated? its
formula?

Answer Posted / sriram

This calculation Applicable for 3 phase fault.

Transformer:

Step 1:
First calculate Full load current
I(F.L)=(KVA*1000)/(V*1.732)
Step 2:
Calculate multiplier factor(M)=100/%Z

Step 3:
I(sc)=I(F.L)* M

Motor

Step 4:
F=(1.732*L*I(#phase))/(c*n*E(line-ground))
step 5:
M=(1/(1+F))
step 6:

I(s.c)sym rms=I(s.c)*M
I(s.c) MOTOR=4*I(s.c)

Total fault current =Is.c(trans)+Is.c(Motor)

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is lc oscillator?

1136


HOW WE CAN REDUCE THE CIRCUIT COMPLEX OF STAR-DELTA STARTER .BECAUSE NOW WE USING ONE TIMER RELAY & THREE CONTACTOR FOR MAIN,STAR & DELTA ?IF ANY IDEAS PLZ POST.THANK U

2437


We have a couple of oil tanks at our plant. One of them does not have a lightning arrester installed. My question is it necessary to install an arrestor on every tank or will this particular one be covered by the arrestor installed on the ajdacent tank, Since all the tanks are close to each other. Basically, I want to know that if these arrestors or protection works in a parituclar area of effect or influence. Thanks

1999


If more than rated DC voltage appears across trip coil of the breaker, what will happen? e.g. in 110V DC circuit system, if voltage across battery terminal showing 121 V

1601


im electrical engineer, could any one help me for FEWA exam questions please ?

1060


Why does the radius of armature is less than the radius of pole shoe?

2105


why the making current is more than then the breaking current and if its true then its about a controling circuit or breaker power contact points

2015


pls tel me the electric train traction motors name plate details like rpm,torue,voltage,amps,watts..ect..

1996


Why single phase induction motors are not self starting ?

1607


can anyone send me some sample question regarding power grid corp

2157


If the feeder rating is 7.5 kw or 10 HP star-delta feeder, MCCB is taken as 63 a, contactors-32 a, how much will be the OLR rating or which range OLR should be considered when we concern about type-2 coordination?

2266


When will you multiply and devide with derating factors to the actual value while sizing the cable?

1884


What is the Nyquist criterion regarding control systems?

1035


how to calculate the mesh earth network resistance in such substation, is there any recommended resistance values with references , thanks!

2278


What are :- AC Distribution Board (Single & Double Front) DC Distribution Boards Distribution Board LT Breaker Panel.

2026