how to measure earth pit resistance
Answer Posted / bhatt
Earth pit resistance is measured by Earth tester, Earth
tester have four terminals P1,P2,C1,C2 i.e. Two potential &
Two Current terminals. while earth pit testing, P2 & C2 are
shorted and C1 connected to current spike(Conductive rod)
which should be drived into soil at around 30 meter
distance from earth pit and P1 is connected to potential
spike(Conductive rod) drived at around 15 mtr away from
earth pit in the direction of current spikes.By rotating
the handle of meter(in old meters) or by pressing test
button (in new type meter) one can get earth resistance.Now
Potential spikes are drived at different locations toward
earth pit and current spike side and a curve between
distance and resistance is plotted. Earth resistance will
be platue of the graph.In this meter current is passed
between earth pit and current spike and potential is
measured between potential spike and earth pit. Ratio
between Voltage measured and current passed thrugh the
earth is the resitance of earth pit.
| Is This Answer Correct ? | 139 Yes | 20 No |
Post New Answer View All Answers
Give details on how you intend to handle a challenging position you are posted to manage unexpectedly as a company staff?
explain the types of drives
i need to give section engineer (electrical engineer) for RRB. Please suggest some book
What is the meaning of HT Trivector Meter ?
how 650 volts creates? where is use?
What is negative sequence over voltage element?
Why sometime AVR and sometime Booster coil is used in Alternator? what is the diferance between AVR & Booster coil due to which they are selected
IF I KNOW THE AREA OF CROSS SECTION OFTHE WIRE , WATTAGE OF THE LOAD ,VOLTAGE SUPPLY WHAT IM GIVING TO THE LOAD AND ALSO POWER FACTOR OF LOAD ....... SO GIVE ME FOR WHAT AMOUNT OF CURRENT I SHOULD USE WHICH TYPE OF CABLE?
What are the advantages and disadvantages of the dc motors?
and gate circuit diagram,amplifier circuit diagram
(In MEP services) HVAC in AC Plant room what else can we provide if the chiller is not considered?
Does the motor power displayed on the Motor name plate is the mechnical power motor delivers or it is consumed power from the system?
a simple c++ program to calculate simple interst with its data members as private
Is it required to lay 2 runs of GI wires along with armoured cables from one power DB Machines of higher rating?
What is the reason of polyphase induction motor tripping suddenly on high current during running at 70% laod? Motor IR , winding resistance & inductance balance. Motor no load current is balance and ok as per mgfr. data.