In RTU Panel we are having several Analogue & Digital
Inputs /Outputs. We are recently facing some problems over
Analog inputs , which are not updating properly (But
Digital Input are updating normally) Can any one tell me
from where the problem is creating , we have checked PLC
CPU card, Analog Input card & we reconfigured ,But still
the issue is there.
Issue :
1. Sometimes Analog values are updating & sometimes not.
2. Analog values are not updating normally , showing some
wrong Values
3. Total dead (0 value)
Analog values are Level & flow measurement from the field
instruments.
(But in field the instruments are working normally &
Displaying the values normally in local display unit)
This problem we are facing in our Water Plant.
If any one experienced this same problem or having any
ideas related to our issue PLS send your valuable
Answers/Replies...
Answer Posted / dhaval jethva
Hi There........
As you have mention the problem,i can say that there is
definitely problem in two things (1) Scaling of that input
(2) Signal wire Coming from field instrument to your RTU
terminal.
If you dont find any problem above then do following Task
(3) if there is problem in only one channel of analog
terminal of RTU then By trial n error of by shuffling the
input you can verify where is the exact problem.
Please tel which i/p you are using Like is it 4 t0 20ma or
0 to 10 V from isolator of directly.
Regards
Dhaval Jethva
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What are the error values can accepted in flow transmitter calibration?could u give any formula for this?
Difference between ultra sonic flow meter
How can we use feedback signal frm rtd for monitoring and in dcs for controlling ,then which type of rtd is sutaible 2 , 3,4wire and why ?
what is intrinscily safe system and where we use?
Why rdt and thermocouple both give different output .and one things more, how to generate ohm or mili volt plz mail me merajalam143545@yahoo.com
typical loop drawing of a simple feedback control comprising of one transmitter and one control
Identification of ss fittings, pilot valves, relief valve.
how do calibrate the valves.. with clear manual
why I need valve guard and whats different between guard and positioner ??
How to calibrate H2s Dectector
Explain the working principle of lvdt?
How can you add value to this Industry if offered the job?
How to Calibrate Ultrasonic Level Transmitter in field
In turbine what does term CDP, NH, HSSOC means.
How a conductivity sensor & analyzer work at boiler, whats the principle & science is beyond this,How conductivity sensor sence & convert signal & move toward analyzer & analyzer show reading in percent? also what is temperature compensate option in conductivity analyzer