why we use DO Fuse in H.T. Line ? What is the purpose of
DO Fuse
Answer Posted / k.prakashchandra
DOLO cut outs are provided to 11KV/433V tr centers and
sometimes to the 11 KV lines.The cut outs can be opened
,removed & re fixed with the help of hickory rods for
replacement of HT fuses of trs and opening of lines.As
they have renewable fuses ,they provide back-up protection
also.They are just like HT cut-outs and a cheap substitute
for GOS. Earlier they were used for protection to power trs
in sub-stations on 110 or 33KV side when they were called
expulsion type fuses.
| Is This Answer Correct ? | 9 Yes | 3 No |
Post New Answer View All Answers
If we need4× 50mm sq cable but it's not available so we can pull 4×25mm sq 2cables
i have gear oil pump with single phase motor.some time its motor starts running in reverse direction rather than forward direction...whats the reason behind this issue. 1- either capacitor is week? 2- or winding is week?
A 400 V, 50 Hz, Δ connected synchronous generator has a field reactance of 0.1 Ω and armature resistance of 0.015 Ω. At full load, the machine supplies 1200 A at 0.8 pf lagging. Under full-load conditions, the friction and windage losses are 40 KW and the core losses are 30 KW. What is the machine’s overall efficiency? Ignore any field circuit losses.
What will happened if the neutral of secondary of Xformer ( Star point) Note it's above KVA rated Xformer
How to megger test 11 kV cable and the acceptance IR value
High speed earth switch operation with diagram
Why the power generated in dams is complex power? Why the generators in dams cannot produce Real power directly (i.e power which has zero reactive part)?
why induction motors are rated at 0.8 power factor.
Single line diagram for dbb (double bus bar)system.
A 500 V shunt motor runs at its normal speed of 250rpm when the armature current is 200A. The resistance of the armature is 0.12 Ω. Calculate the speed when a resistance is inserted in the field reducing the shunt field to 80% of normal value and the armature current is 100A.
In ups static switch if i gives the supply at output end it will open the circuit in stactic switch or not if it will open then how it operates.
How can we calculate ac current from the given DC current when AC voltage is given?
What is the tipical Online UPS input voltage for 20 KVA load ( 3 Phase or 1 Phase )? Why ? Explain it...?
what is the difference between the characteristics of two different phase bushing of any transformer
On what cycle does thermal power plant operate?